Laserfiche WebLink
be required in order to determined if any unauthorized release has occurred. <br />Sampling is required and must be completed under EHD permit. (CCR Title <br />23 section 2660 (1)(k)) <br />5. The tank and line monitoring system must be installed which is found listed in <br />LG113A and must meet the requirements of CCR Title 23 section 2666. <br />This monitoring system must also provide pump shutdown upon leak <br />detection per CCR Title 23 section 2666 (c). <br />6. If any evidence of corrosion is noted by the special inspector during the <br />inspection of the underground tank CCR Title 23 section 2660(n) which <br />refers to section 2635 (2a) (2b) will apply to a corrosion protection system. <br />7. Dispenser pans are required if any work is done to the piping and dispenser <br />systems. <br />If you have any questions regarding this matter, please contact me at (209) 468- <br />3446. <br />Karen Furst, M.D., M.P.H. <br />Health Officer <br />Doug Wilson, Supervising R.E.H.S. <br />Environmental Health Division <br />cc: Tosco Marketing Co. <br />DW/dw <br />