Laserfiche WebLink
9. Spill/Overfill Containment Boxes <br /> Test Method Developed By: ❑Tank Manufacturer ❑x Industry Standard ❑Professional Engineer <br /> Test Method Used: ❑Pressure ❑Vacuum ❑x Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:±0.002 <br /> Spill Box# 87 Spill Box# 87s Spill Box# 91 Spill Box# <br /> Bucket Diameter: 11" 11" 11'• <br /> Bucket Depth: 14" 14" 14" <br /> Wait time: 15 min 15 min 15 min <br /> Test Start Time: 9:45 9:45 9:21 <br /> Initial Reading: 7.7179 5.2420 76641 <br /> Test End Time: 10:00 10:00 9:36 <br /> I--- <br /> Final Reading: 7.7174 5.2423 7.6641 <br /> 1 1 -- T — — <br /> Test Duration hh:mm 00:15 00:15 00:15 00:00 <br /> Chane in Reading: <br /> g: -0.0005 0.0003 — 0.0000 0.0000 <br /> Pass/Fail Threshold or Criteria: ±0.002 ±0.002 ±0.002 ±0.002 <br /> Test Result. *Pass 0 Fail <br /> Pass Fail Pass O Fail O Pas�,i " �'..<` <br /> Comments: <br /> 7 of 7 <br />