Laserfiche WebLink
9. SpilllOverfill Containment Boxes <br /> Test Method Developed By. ❑Tank Manufacturer 0Industry Standard ❑ Professional Enoineer <br /> Test Method Used: ❑ Pressure ❑vacuum 0 Hvdrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution::0.002 <br /> Spill Box# 87M Spill Box# 87S Spill Box#91 Spill Box# <br /> Bucket Diameter: <br /> Bucket Depth: -- -- 14" 14" 14" <br /> Waft time: 16 min 15 min - r 15 min 15 min <br /> Test Start Time: 10:06 9:33 9:33 <br /> Initial Reading: -- 6.4630 - _ 5.4066 -- -_ 6.2314 - <br /> Test End Time: 10:21 9:46 9:46 <br /> Final Reading: 6.4630 5.4053 6.2308 <br /> Test Duration(hh:mm): 00:15 00:15 00:15 00:00 <br /> Change in Reading: 0.0000 -0.0003 -0.0006 0.0000 <br /> Pass/Fali Threshold or Criteria: :0.002 :0.002 :to 002 :0.002 <br /> TestFt9sult: ®Pass O Fail. ® Pass O Fail ® Pass O Fail ® Pass O Fail <br /> Comments: <br />