8. Fill Riser Containment Sump Testing <br /> Test Method Developed By: ❑Tank Manufacturer ©Industry Standard <br /> Q Professional Engineer <br /> Test Method Used: ❑ Pressure ❑Vacuum <br /> ® Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:±0.002 <br /> Fill Sump#87M Fill Sump# 87S Fill Sump# 91 FIII Sump Of <br /> Sump Diameter: 48" 48" <br /> 48" <br /> Sump Depth 49" 46" 41„ <br /> Height from Tank Top to Top of 12" - - <br /> Highest Piping Penetration: 15" 14„ <br /> — -- <br /> eightfrom Tank Top to -- ---- <br /> Lowest Electrical Penetration: 71 14" 21„ <br /> Condition of sump prior to '--- - ---------- <br /> testing: OK OK OK -------OK-----: <br /> Portion of Sump Tested: 1s" 18" 17" <br /> Sump Material: Fiberglass Fiberglass Fiberglass <br /> Wait time: 15 min 15 min <br /> 15 min 15 min <br /> Test Start Time: 9:33 8:68 ----- ----- -- -- <br /> 8:68 <br /> ----- --------- <br /> Initial Reading: 0.2916 1.5960 <br /> 1.6745 <br /> Test End Time 9:48 9:13 9:13 <br /> Final Reading: 0.2913 1.5964 1.6735 <br /> Test Duration(hh:mm): — 00:16 00:15 00:15 00:00 <br /> Change in Reading: -0.0003 ---0.0004-- -- -0.0010 0.00000000----- --- - <br /> Pass/Fall Threshold or Criteria: 30.002 ±0.002 ±0.002 ±0.002 <br /> Test Result: ®'Pass 0 Fail ®Pass 0 Fail 0 Pass 0 Fail 0 Pass 0 Fail <br /> Is there a sensor in the sump? — <br /> Yes Yes Yes Yes <br /> Does the sensor alarm when - <br /> either product or water is N/A N/A NIA N/A <br /> detected? <br /> Was sensor removed for - --- --- --- <br /> testing? *Yes 0 No 0 NA *Yes 0 No 0 NA *Yes 0 No 0 NA ®Yes 0 No 0 NA <br /> Was sens-On properly replaced and verified functional after 0 Yes 0 No ®NA 0 Yes 0 No 0 NA 0 Yes 0 No ® NA 0 Yes 0 No 0 NA <br /> testing? <br /> Comments: <br />