Laserfiche WebLink
E. Reporting FormaRor monitoring: (cont.) 0 <br /> The TLS System has four modes of operation - Leak Detection, Tank Detection, <br /> Interstitial/Piping Sump Lead Detection and Automatic Delivery Reporting. When the <br /> leak monitor mode is activated, the TLS System continuously monitors fuel levels in each <br /> tank and can detect losses of 0.2 gph. An hourly report on each tank shows temperature- <br /> compensated inventory changes to 0.1 gallon based on inventories when the tank leak <br /> mode is initiated. The Leak Monitor is activated through a push-button mounted on the <br /> front panel, or remotely through the RS-232 Telecommunications Interface. <br /> The Tank Inventory Report presents the current status of each tank. It provides station <br /> location, date and time, volume and level of fuel, water level and temperature. <br /> Interstitial/Piping Sump Leak monitoring will be provided using two liquid sensors placed <br /> in the double wall tank annular space and in the tank manhole space. The LED display <br /> on the TLS console will flash indicating the alarm cause and location. <br /> The Automatic Delivery Increase Report features are generated two minutes after fuel <br /> is delivered to the tank. The printout includes date, time, volume and temperature before <br /> and after the increase and the net increase of inventory. <br /> F. Describe the preventative maintenance schedule for the monitoring equipment. <br /> Note: Maintenance must be in accordance with the manufacturers' maintenance <br /> schedule but not less than every 12 months. <br /> All equipment used in implementing the monitoring program shall be installed, <br /> calibrated, operated and maintained in accordance with the manufacturer's instructions, <br /> including routine maintenance and service checks. The system is inspected once per <br /> calendar year by a third party in accordance with Article 5, Title 23, CCR. Copies of <br /> the recertification report shall be sent to the administering agency and copies will be <br /> maintained on site. <br /> G. Describe the training necessary for the operation of UST system, including piping, <br /> and the monitoring equipment: <br /> The key personnel on the site are trained for responding appropriately to any major <br /> catastrophe. A training program conducted by the training department of Pacific Bell <br /> provides the information to the key personnel regarding emergency telephone numbers, <br /> reporting requirements, location of emergency equipment and evacuation procedures. <br /> All personnel involved with maintaining the monitoring system have been trained and <br /> certified by the manufacturer of the equipment in accordance with Article 5, Title 23, <br /> CCR. <br /> pg. 9 <br />