Laserfiche WebLink
CERTIFICATE OF UNDERGROUND STORAGE TANK SY'S- ,M,TESTINfTGT`` <br /> gal.` .Ili Hr-ALlf� <br /> NDE ENVIRONMENTAL CORPORATION <br /> 20000 Mariner Avenue, Suite 500 03 J�l! <br /> Torrance, California 90503 - I PH Z 4 1 <br /> (310) 542-4342 <br /> Test Date: 5 May 1993 Work Order#: 960996 <br /> Client: BOYETTE PETROLEUM CO. Site: SOUTH COUNTRY FOOD & GAS <br /> P.O. BOX 1099 1305 S. ESCALON <br /> SALIDA CA 95368 ESCALON CA 95320 <br /> Attn: CARL BOYETTE <br /> The following tests were conducted at the site described above in accordance with all applicable portions of Federal,NFPA,and Local regulations. <br /> TANK SYSTEM INFORMATION <br /> TankTank Product Vapor Recovery <br /> Tank Capacity Diameter Level Tank <br /> No. Gallons Inches Product inches Material Stage I Stage II <br /> 1 10, 310 95 SUPER 46 .00 STEEL COAX BALANCE <br /> 2 10, 310 95 MIDGRADE 41.00 STEEL COAX BALANCE <br /> 3 8, 101 95 UNLEADED 64 . 00 STEEL COAX BALANCE <br /> TESTING RESULTS <br /> VPLT Wetted Vent & Leak Leak <br /> Volume Portion Ullage Vapor Product Detector Detector <br /> Tank Change of Tank Test Lines Lines Present? Results <br /> No. (gph) Pass/fail Pass/Fail Pass/Fail Pass/Fail Yes/no Pass/Fail <br /> 1 0 . 005 PASS PASS PASS PASS YES PASS <br /> 2 -0 . 018 PASS PASS PASS PASS YES PASS <br /> 3 -0 . 004 PASS PASS PASS PASS YES PASS <br /> NDE appreciates the opportunity to serve you,and looks forward to working with you in the future.Please call any time,day or night,when you need us. <br /> NDE Customer Service Representative Testing conducted by <br /> F. MILLER /22 M. LEVESQUE <br /> Reviewed by: Technician certification no.: <br /> Be amin Alicea 1405 <br />