Laserfiche WebLink
Test Date: 5 May 1993 Work Order#: 960996 <br /> TANK TESTING DATA <br /> Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6 <br /> Product: SUPER MIDGRADE UNLEADED <br /> True Capacity-gal: 10, 310 10, 310 8, 101 <br /> Manifolded tanks: NO NO NO <br /> Manifolded Vents : YES YES YES <br /> Tank Bottom <br /> to top of fill-in: 127 134 133 <br /> Fill pipe length-in: 32 39 38 <br /> Tank diameter-in: 95 95 95 <br /> Tank Bottom <br /> to top of grade-in: 134 140 148 <br /> Fill pipe diameter-in 4 4 4 <br /> Fluid Level-in: 46 . 00 41. 00 64 .00 <br /> Fluid Volume-gal : 4,948 j 4, 260 5 , 805 <br /> Water in tank-in: 0 0 0 <br /> Specific Gravity: 0 .748 0 .746 0 .743 <br /> Tank Construction: STEEL STEEL STEEL <br /> OFT/UFT: UFT UFT UFT <br /> No. thermistor: 5 5 5 <br /> Ground Water level-in <br /> How determined: NO WELL NO WELL NO WELL <br /> Test start time: 11:39 11:45 11: 50 <br /> Test finish time: 13 :40 13 : 50 16: 02 <br /> Total temperature <br /> change (degrees F) : -0 . 082 -0 . 018 -0. 498 <br /> Total fluid level <br /> change (inches) : -0 . 001 0. 000 -0. 007 <br /> Leak Rate (GPH) : 0 .005 -0.018 -0.004 <br /> Pass/Fail: PASS PASS PASS <br /> NDE Environmental Corporation-20000 Mariner Avenue Ste 500-Torrance,CA.90503-(310)542-4342 Page I <br />