Page 2 of 14 ESR-1917 <br /> breakout strength in tension for uncracked concrete, lightweight or normal-weight concrete on steel deck floor and <br /> calculated according to ACI 318 Section D.5.2, must be roof assemblies, as shown in Figure 5, is given in Table 3. <br /> further multiplied by the factor W,.°„as given by the following 4.1.7 Requirements for Static Concrete Breakout <br /> equation: Strength of Anchor in Shear, V,or V,,r: Static concrete <br /> c breakout strength shear capacity must be calculated in <br /> Wes= ci6 (1) accordance with ACI 318 Section D.6.2 based on the values <br /> provided in Tables 3 and 4. The value of 1,used in ACI 318 <br /> Equation(D-24)must taken as no greater than hµ <br /> whereby the factor W.,,, need not be taken as less 4.1.8 Requirements for Static Concrete Pryout Strength <br /> than 1.Sh°, . For all other cases, Wc,,,= 1.0. Values for the of Anchor in Shear, V, or V.: Static concrete pryout <br /> C. strength shear capacity must be calculated in accordance <br /> critical edge distance c„must be taken from Table 3 or Table with ACI 318 Section D.6.3,modified by using the value of k„ <br /> 4 provided in Tables 3 and 4 of this report and the value of N, <br /> or N,, as calculated in Section 4.1.3 of this report. For <br /> 4.1.5 Requirements for Static Pullout Strength in anchors installed in the soffit of structural sand lightweight or <br /> Tension: The pullout strength of the anchor in cracked and normal-weight concrete over profile steel deck floor and roof <br /> uncracked concrete, where applicable, is given in Tables 3 assemblies,as shown in Figure 5,calculation of the concrete <br /> and 4. In accordance with ACI 318 Section D.5.3.2, the pryout strength in accordance with ACI 318 Section D.6.3 is <br /> nominal pullout strength in cracked concrete must be not required. <br /> calculated according to the following equation: 4.1.9 Requirements for Minimum Member Thickness, <br /> Ff� Minimum Anchor Spacing and Minimum Edge Distance: <br /> (lb, psi) (2) In lieu of ACI 318 Section D.8.3, values of c,,,,, and s,,,,,as <br /> 2,500 given in Tables 2 and 3 of this report must be used. In lieu of <br /> ACI 318 Section D.8.5,minimum member thicknesses h,,,,as <br /> given in Tables 3 and 4 of this report must be used.Additional <br /> combinations for minimum edge distance c,n,and spacing s,,,,, <br /> may be derived by linear interpolation between the given <br /> No = N°, 1 2 (N, MPa) boundary values. (See Figure 4.)The critical edge distance <br /> at corners must be minimum 4h„in accordance with ACI 318 <br /> Section D.8.6. <br /> In regions where analysis indicates no cracking in 4.1.10 Requirements for Seismic Design: For load <br /> accordance with ACI 318 Section D.5.3.6,the nominal pullout combinations including earthquake, the design must be <br /> strength in tension must be calculated according to the performed according to ACI 318 Section 0.3.3 as modified by <br /> following equation: Section 1908.1.16 of the IBC,as follows: <br /> _ f CODE ACI 318 D.3.3. CODE EQUIVALENT <br /> NP''r`-N, .500 (Ib,psi) (3) SEISMIC REGION DESIGNATION <br /> Moderate or high Seismic Design <br /> IBC and IRC seismic risk Categories <br /> C,D, E,and F <br /> Moderate or high Seismic Zones <br /> N N ��� (N, MPa) UBC seismic risk 28,3,and 4 <br /> w'r�_ °. 17.2 <br /> The nominal steel strength and the nominal concrete <br /> breakout strength for anchors in tension, and the nominal <br /> Where values for N°Por N°,are not provided in Table 3 concrete breakout strength and pryout strength for anchors in <br /> or Table 4, the pullout strength in tension need not be shear,must be calculated according to ACI 318 Sections D.5 <br /> evaluated. and D.6, respectively, taking into account the corresponding <br /> The pullout strength in cracked concrete of the carbon steel values given in Tables 3 and 4.The anchors comply with ACI <br /> KB-TZ installed in the soffit of sand lightweight or normal- 318 DA as ductile steel elements and must be designed in <br /> weight concrete on steel deck floor and roof assemblies, as accordance with ACI 318 Section D.3.3.4 or D.3.3.5. The <br /> shown in Figure 5,is given in Table 3.In accordance with ACI nominal pullout strength N°,,,,and the nominal steel strength <br /> 318 Section D.5.3.2,the nominal pullout strength in cracked for anchors in shear V„o„must be evaluated with the values <br /> concrete must be calculated according to Eq. (2), whereby given in Tables 3 and 4.The values of N°.„must be adjusted <br /> the value of Np,,,,.,.,,must be substituted for N, The use of for concrete strength as follows: <br /> stainless steel KB-TZ anchors installed in the soffit of f, <br /> concrete on steel deck assemblies is beyond the scope of N ;,. ,=N,,,,, (Ib, psi) (4) <br /> this report.in regions where analysis indicates no cracking in ° r ° YYY 2,500 <br /> accordance with ACI 318 Section D.5.3.6,the nominal pullout <br /> strength in tension may be increased by W,„ as given in <br /> Table 3. W,,is 1.0 for all cases. Minimum anchor spacing N,,,;, ,=N ,,�,f” IN, MPa) <br /> along the flute for this condition must be the greater of 3.0h„ ° r ° 17 2 <br /> or 1'/,times the flute width. <br /> 4.1.6 Requirements for Static SteelSheaTCapacity V,�Itti— If no values for N°,,,,or V,,,,,are given in Table 3 or Table <br /> lieu of the value of V,as given in ACI 318 Section D.6.1.2(c), 41 the statfe-designstrength values-goverr. (See-Sections`- <br /> the values of V,given in Tables 3 and 4 of this report must be 4.1.5 and 4.1.6.) <br /> used. The shear strength V, ,,as governed by steel failure 4.1.11 Structural Sand Lightweight Concrete: When <br /> of the KB-TZ installed in the soffit of structural sand structural lightweight concrete is used, values determined in <br />