Laserfiche WebLink
09'26.2002 11:19 FAX 125 251 8782 BARGHAUSEN 0036 <br /> 091'13/2002 11:18 523 <br /> IPF INC <br /> PAGE 05 <br /> AlItech <br /> 17759 Buttz-r:up circle, Sonora, CA 95370 <br /> Phone: 209-532-7320; FRc_ 209-533-2650 <br /> California Tank Tester: 90-1068 <br /> California Contractor 623b41 A-Hoz <br /> al teel mlode_com <br /> ppipwaSIOm TEST DATA SHEET for PIMG <br /> Facility: Costco 658 Date: Sep. 12, 02 <br /> Address: 3254 Grant Line Rd. <br /> City: Tracy CA <br /> FaC lity contact: W.A. Craig Phone: <br /> L.I.A.: San Joaquin-, Michelle L.I.A. Phone: 209-468-3451 <br /> 14asstech Accu-Rite Pressurized Pip' g Tester <br /> Product Reg 1 Prem <br /> Turbine isolation method * BV BV <br /> Dispenser isolation method Im -Imp <br /> Test pressure, PSI 50 50 <br /> Initial cylinder level 0.0500 0.0500 FEE I <br /> Final under level 0.0490 0.0495 <br /> Time Started 1130 1200 <br /> Time Completed 1200 1230 <br /> Total test time, minutes 30 30 <br /> RP.sult: volume change in GPH 0.002 0.001 <br /> conclul!i0n: 'Pass/Fail PASS Pass <br /> Leak Detector Test: Paas Pass <br /> * Pass/Fail threshold is 0.01.x]0 GPM per Manufacturer's protocol <br /> Remarks: The line from Reg 1 feeds the row of islands closest to the building. <br /> The line from Reg 2 feeds the row of it3lands closest to the taroks_ There is a <br /> crossover line that permits use of either regular turbine to feed all islands in <br /> case of a failure. Testing either line with this crossover open, allows testing of <br /> all the regular lines at once_ The ball valve in the crossover was closed prior to <br /> testing line leak detectors. <br /> Test tech: � � - Mike Dotten, License 98-106S F.c+.3f 6!}003 <br />