09/26%2002 14:50 FAX 425 251 8782 BARCH USEN ,_ Q037 <br /> -09/13/2002 11:18 523 <br /> IPE INC 'PAGE 08 <br /> A11tech <br /> 17759 Buttercup Circle, Sonora, CA 95370 <br /> Phone: 209-532-7320, Fax.: 209-533-2650 <br /> California Tank Tester: 90-1068 <br /> c-al fornix Contractor 623541 A-Haz <br /> alltech r�z? ode.com <br /> Precision Test Data Skeet for Line Leak Detectors <br /> Vaporless LDT-890 <br /> Facility: Costco 658 Date: Sep. 12, 02 <br /> Address_ 3250 !Grant Line Rd. <br /> City: Tracy CPA <br /> Facility contact: N.A. Craig Phone: 707-693-2929 <br /> L.I.A.: San Joaq; Michelle L.I.A. Phone: 209-468-9847 <br /> Product 4 Re 1 Reg2 Prem <br /> Turbine manufacturer FE P FE P FE P <br /> Leak Detector mfr Red J Red J Va <br /> L.D. search presspre 10 10 20 <br /> Ste -throu time- seconds 4 3 3 <br /> Turbine op eratin ressure 38 38 38 <br /> Line holding pressure- psi 19 20 35 <br /> Bleed back test-- ml 800 1100_ 1200 <br /> 10 psi flowuanti - m1 95 95 _ 95 <br /> Leak detector stays tripped? Yes Yes Yes <br /> C`.OnClu�lion: * Pass/Fail Pass Pass Pass <br /> Pass— Leak Dear stays in slew-flow during GFH Test; <br /> Fail = Leak Detector steps through to allow full pump pressure during GFH <br /> Test: <br /> Remarks: Reg 1 is the tank closest to the islands and fuels the dispenser row <br /> closest to tate store_ Reg 2 is tate center tamk and fuels the dispenser row <br /> closest to tate U ks. The Premium tank fuels all dispensers. <br /> Test tech: / Mike Dotter.License 90-1068 r,6,r;me <br />