Laserfiche WebLink
We <br /> San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sigov.org/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Costco Wholesale#38 1616 E Hammer Ln, Stockton March 02, 2017 <br /> UST System Observations <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status ❑V ❑R o COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status ❑V ❑R ❑COS <br /> 324 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST o V ❑R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored o V ❑R ❑COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 329 HSC 25298 Failed to comply with permanent closure requirements o V ❑R ❑COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system n V c R o COS <br /> Single-Walled Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve o V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) o V o R �COS <br /> Other Violations <br /> 2010 See below Unlisted Administration/Documentation violation V i R COS <br /> 2030 See below Unlisted Operations/Maintenance violation ❑V ❑R ❑COS <br /> 2060 See below Unlisted Design/Construction violation n V o R o COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item # Remarks <br /> 107 CCR 2632(d)(1)(C) Plot plan/site map not submitted or failed to completely show where monitoring is performed. <br /> An accurate UST Monitoring Site Plan was not submitted. Change under Monitoring Legend (C)fill sump sensor <br /> from 112 to 323 sensor; change (H)fill sump sensor 352 to 323 sensor; and change(1)vent sump sensor from 208 <br /> to 323 sensor. A site plan must be submitted identifying the locations where monitoring will be performed. <br /> Immediately log into the California Environmental Reporting System (CERS)at http://cers.calepa.ca.gov/and upload <br /> a copy of the UST Monitoring Site Plan. <br /> This is a minor violation. <br /> 305 HSC 25290.1(e)VPH monitoring of the interstitial spaces of the UST system is not maintained. <br /> The S3 sensor was in sensor fault alarm upon arriving at the site and failed when tested.. The interstitial space of <br /> the UST shall be maintained, as designed, under constant vacuum such that a breach in the primary or secondary <br /> containment is detected before the hazardous substance is released into the environment. The service technician <br /> disconnected the wire seal pack, cut a section of the wires, reconnected the wires and retested the S3 sensor <br /> during the inspection. The S3 sensor passed. <br /> This was corrected on site. <br /> This is a repeat violation, Class Il. <br /> FA0001705 PRO518624 Scoot 03/02/2017 <br /> EHD 23-01 Rev.09/22/16 Page 3 of 4 Underground Storage Tank Program OIR <br />