Laserfiche WebLink
ITT5 Integrity Took Testing Systems, Inc. <br /> e6- 7657 <br /> / O, 000 O/EStZ TEST DATA AND <br /> C, 000 6.4S TEST RESULTS <br /> September 21 , 1987 <br /> ITCEM9 <br /> Mr. Gary ShearingcStockton Steel ;:P r2 Q 1987 <br /> P. 0. Box 8429 <br /> Stockton, California 95208 <br /> ENVIRCMENTAL HEALTH <br /> Dear Mr. Shearing : FERMII/SERVICES <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less titan . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action . <br /> TANK II/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 10,000 Unlead. Gas . -. 03658 Yes <br /> South 10 ,000 Diesel Fuel -. 00702 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sinc�y, <br /> I <br /> rank Kese <br /> Certified es r <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 96206 (209) 466.8036 <br />