Laserfiche WebLink
/RECENED <br /> JAN 1 a tu10 <br /> STOCKTON P j��ON EQUIPMENT CO. INC. <br /> 808 N STREET <br /> STOCKTON, CA 95205-4152 <br /> PHONE 209.464.8333 FAX 209.464.8349 <br /> LDT-890 LEAK DETECTOR TEST RECORD <br /> CUSTOMER: Riverpoint Landing Marina Date: January 13,2010 <br /> LOCATION: 4950 Buckley Cove <br /> CITY: Stockton STATE: CA ZIP: <br /> - TECHNICIAN: Mike Jones -- <br /> Submersible Pump Identification <br /> Manufacturer Model Serial Number <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> Fe Petro STP-MLD Gasoline S/N 08060805 <br /> Diaphragm-type <br /> Piston-type <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 27 psi (Purging Test System) <br /> 2. Gallons per hour rate 3 (Leak Test,Phase I) <br /> ;ur�tvith-p4"- shutoff 26 ___ psi (Leak TestPhawl) <br /> 4. Bleed-Back Test with pump off 450 ml (Bleed-back Test) <br /> 5. Step-through time to full flow 80 sec seconds (Step-through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase II)Yes X No <br /> LEAK DETECTOR TEST <br /> Note: Pass=Leak detector fits test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Forth 890C <br />