Laserfiche WebLink
w <br /> From: Raymond von Flue [EH] [mailto:rvonflue_@sjcehd.com] <br /> Sent: Thursday, December 05, 2013 4:38 PM <br /> To: Jonathan Smith <br /> Cc: Kasey Foley [EH]; wng@sjcehd.com; artl@mrbec.com; mikeb@mrbec.com; jerrod.herron@pilottravelcenters.com; <br /> cjohnsonPcore-eng.com <br /> Subject: RE: Special Application Containment Sump <br /> Jonathan, <br /> After reviewing the attachment from Mr. Don K. Mukai,the engineering specification as listed in the section below is <br /> missing the following information: <br /> No mention of the materials used to construct the secondary containment system that will provide sufficient thickness, <br /> density,corrosion resistance to prevent structural weakening or damage to the secondary containment system as a <br /> result of contact with any released hazardous substance. <br /> No mention that the secondary containment will be constructed to contain the listed volumes for the existing dry <br /> annular primary piping containment system at this facility. <br /> i <br /> According to CCR, section 2631.1 (b): For underground storage tank system components installed on or after July 1, <br /> 2004,the applicable approvals required in subsections 2631 (b) and (d) shall include a list of the compatible products F <br /> tested and the measured permeation rates, if such testing is required by the industry code or engineering standard used <br /> to evaluate the component. These results shall be provided to the local agency upon request. <br /> I <br /> Was any testing required to be conducted by Mr. Mukai by industry code or engineering standard to evaluate the <br /> containment sump? If so, please submit these results. <br /> Raymond von Flue <br /> Lead Sr. REHS, CUPA Programs <br /> San Joaquin County <br /> Environmental Health Dept. <br /> 8 <br /> 1865 E. Hazelton Ave. <br /> Stockton, CA 95205-6232 <br /> (209)468-9848 <br /> From: Jonathan Smith [mailto:JSmith@sbravo.com] <br /> Sent: Thursday, December 05, 2013 3:49 PM <br /> To: Raymond von Flue [EH] <br /> Subject: RE: Special Application Containment Sump <br /> Importance: High <br /> Hello Raymond, <br /> Getting back to you regarding the B-830 series sump line. We specialize only in Secondary Containment, with <br /> containment sumps and entry fittings that are not a component of the primary containment system. This <br /> product falls under the provision found at CCR Title 23, Article 3, section 2031(d), which states: <br /> 2 <br />