Laserfiche WebLink
Sep , 26. 2003 H:55AM LC`FRVJCFS No - 2685 P . 4 <br /> SWRCS,Jarr,ary 2002 <br /> Page 3 of 3 <br /> 7, UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: <Tank Manufacture <br /> indUStry Standard <Prafessignal Engineer <br /> Other(Specify) <br /> Test Method used- <Pressure #Vacuum <br /> <Qther(S BCify} Hydrostatic <br /> Test Equipment Used; Incon TS-ST <br /> Equipment Resolution: 0.0001" <br /> UDC ; Disp.7-8 UDC# Disp. 11-12 UDC# UDC# <br /> UDC Manufacturer: Bravo bravo <br /> UDG Material: Steel <br /> UDC Depth: Steel <br /> 9" <br /> Height from UDC Top to Top of <br /> Highest Piping Penetration; 1" <br /> Height from UDC Top to Lowest 1 <br /> Electrical Penetration; 111 <br /> Condition of UDC prior to testing: GOODi" <br /> portion of UDC Tested; GO{7b <br /> ALL AL4 <br /> Does turbine shut down when <br /> sump sensor detects liquid(both <br /> product and water)? <Yes <No 4 NA <Yes < <br /> Turbine shutdown response timeNA NA No NA <Yes <No <NA <Yes <No <NA <br /> Is system programmed for fail-safe <br /> shutdown?` <br /> <Yes <No �NA <Yes <No NA <Yes <No < <br /> Was fail-safe vsrifled to be <Y@s <No <NA <br /> operational?" <Yes <No <br /> NA <Yes <N <br /> fl 1�NA <Yes <No <NA <Yes <No <NA <br /> Wait time between applyirn ._.. <br /> pressure/vacuum/water and <br /> starting test 15 min <br /> Test Start Time: i5 min <br /> 2:04 2A4 <br /> Ini4'aP Reading: 1,9475 1.4548 <br /> Tes7E—nd Time: 219 <br /> Final Reading: 2'19 <br /> 1.9482 1.4551 <br /> Test Duration- 15 min 15 min <br /> Change in Reading: 0.0003 4.0408 <br /> PasS/Fail Threshold or Criteria. _0.002 -0,002 <br /> Test Result: . Pass <Fail Wags <Fail <Pass <Fail < <br /> Was Sensor rcmovedfor testing? CYer, <NoPass <Fail <br /> Was sensor property repl9ced ane NA <Yes <No Nq <Yes <No <NA <Yes <No <Nq <br /> verlfled functional after testing? <Yes <No <br /> NA <Yos <No +J NA <Yes <N0 <NA <Yes <Na <NA <br /> Cornrnents–(include information on repairs made prior to resti nji,,and recommended ollow_& fpr ailed tests <br /> UDC Dlsp's.#7-$,&11-12 (RETEST) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested. Ifthe answer to Ya3r of the+questions <br /> indicated with an asterisk(*)is"NO"or"N.A,",the entire UDC must be tested. (See SWR,CB LG-160) <br />