Laserfiche WebLink
SWRCB,January 2002 Page of__ <br /> 7. UNDER-DISPENSER CONTAINMENT (UDC)TESTING <br /> Test Method Developed By: L UDC Manufacturer Industry Standard X Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: J Pressure Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> Kii <br /> UDC# 1&2 UDC#3&.4 UDC#5&6 UDC#7&8 <br /> UDC Manufacturer: Bravo Bravo Bravo Bravo <br /> UDC Material: Coated Steel Coated Steel Coated Steel Coated Steel <br /> UDC Depth: 9" 9" 9" 9" <br /> I leight from UDC Bottom to Top Enters from bottom Enters from bottom Enters from bottom Enters from bottom <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to Enters from bottom Enters from bottom Enters from bottom Enters from bottom <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry Dry Dry <br /> testing: <br /> Portion of UDC Tested' Water Level 8" Water Level 8" Water Level 8" Water Level 8" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both No No No No <br /> product and water)?* <br /> Turbine shutdown response time NIA NIA NIA N/A <br /> Is system programmed for fail- Yes Yes Yes Yes <br /> safe shutdown?` <br /> Was fail-safe verified to be No No No No <br /> operational?* <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> water and starting test <br /> Test Start Time: 10:57 11:02 11:07 11:12 <br /> Initial Reading (RI): .001 .001 .001 .001 <br /> Test End Time: 11:27 11:32 11:37 11:42 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading (RF—RI): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005130 Minutes .005130 Minute_s .005130 Minutes <br /> Test Result: Pass Pass Pass Pass <br /> Was sensor removed for testing? *NA *NA *NA *NA <br /> Was sensor properly replaced and *N/A *NIA *NIA *NIA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing and recommended fallow-up for failed tests) <br /> *Bravo System Float&Chain for Fire Valve shut off only. No Liquid Sensors in UDC's. <br /> ' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />