Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 8. UNDER-DISPENSER CONTAINMENT(UDC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Sped) <br /> Test Method Used: Pressure ❑'Vacuum X Hydrostatic <br /> I Other(Specify) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> .1 <br /> UDC#9&10 UDC#11&12 UDC# UDC# <br /> UDC Manufacturer: Bravo Bravo <br /> UDC Material: Coated Steel Coated Steel <br /> UDC Depth: 9" 9" <br /> Height from UDC Bottom to Top Enters from bottom Enters from bottom <br /> of Hi hest Piping Penetration: <br /> Height from UDC Bottom to Enters from bottom Enters from bottom <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry <br /> testing: <br /> Portion of UDC Tested' Water Level 8" Water Level 8" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both No No <br /> product and water)?' <br /> Turbine shutdown response time NIA NIA <br /> Is system programmed for fail- <br /> safe shutdown?' Yes Yes <br /> Was fail-safe verified to be No No <br /> operational?* <br /> Wait time between applying 5 Minutes 5 Minutes <br /> water and starting test <br /> Test Start Time: 11:47 11:52 <br /> Initial Reading(R,): .001 ,001 <br /> Test End Time: 12:17 12:22 <br /> Final Reading(RF): .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes <br /> Change in Reading(RF-Ri : 0 0 <br /> Pass/Fail Threshold or Criteria: .005130 Minutes ,005130 Minutes <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? *NA *NA <br /> Was sensor properly replaced and <br /> verified functional after testin-? NIA NIA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> *Bravo System Float&Chain for Fire Valve shut off only. No Liquid Sensors in UDC's. <br /> If the entire depth of the UDC is not tested,specify how much was tested, If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />