Laserfiche WebLink
ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Shell Oil Date: 6/23/04 <br /> 7910 Lower Sacramento—Stockton,CA. 95210 <br /> Test Method Developed By: ❑Spill Bucket Manufacturer 1] Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑O Hydrostatic <br /> ❑Other('Specify) <br /> Equipment Resolution: <br /> Test Equipment Used:Measuring tape Exam le- 1/8"increments <br /> Spill Box#87 Spill Box#89 Spill Box#91 Spill Box#Waste Oil <br /> Bucket Capacity in gallons: 15-F 5-V 15-F 5-V 15-F 5-V 5 <br /> Bucket Depth: 10 5 10 5 10 5 5 <br /> Wait time between filling with 15 min 15 min 15 min 15 min 15 min 15 min 15 min <br /> water and startian test: <br /> Test Start Time: 8:30 am 8:30 am 8:30 am 8:30 am 8:30 am 8:30 am 8:30 am <br /> Initial Reading ) 3 '/." 4'/z" 4`V,," 5„ 6„ 4„ 43/4„ <br /> (RI <br /> Test End Time: 9:30 am 9:30 am 9:30 am 9:30 am 9:30 am 9:30 am 9:30 am <br /> Final Reading(RF): 31/4" 4%Z" 41/211 5" 6" 4" 43/4" <br /> Test Duration: 1 hour 1 hour 1 hour 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(RF-RI): None None None None None None None <br /> Pass/Fail Threshold or Criteria: ZERO LOSS ZERO LOSS ZERO LOSS ZERO LOSS <br /> Test Result: 0 Pass N Pass ❑x Pass ® Pass <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> All Buckets Passed. <br /> Tested By: Service Station Systems, Inc. Technician: Ron W. <br /> Contractor License: 485184 <br />