Laserfiche WebLink
0 <br />Quality Petroleum Equipment <br />LOT - 890 Test Form <br />0 <br />RECEIVEC <br />MAY 21 2015 <br />ENVIRONMENTAL <br />HFA! Tu r1FDA GTIAC�IT <br />Test Information <br />Date: 4/09/2013 Test Company: Mid Valley Consulting & General Eng. <br />Telephone: 530.749-9892 Contact: James Dav <br />Site ID FAST AND EASY Address: 10878 N. HWY 99 <br />City: STOCTON State: <br />Type of Test Equipment: VMI LICIT - 8901AF <br />Submersible Pump identification <br />MFG: RED JACKET Model No: P150S1 Serial No: 1695 <br />Leak Detector Identification <br />MFG: RED JACKET Model No - <br />Re lacernent <br />o:Replacement Leak Detector Identification <br />MFG _ Model No: <br />FXIV Serial No: 5350 <br />Serial No <br />Line Conditions <br />I. Type of Pipe: FRP 2. Diameter of Pipe: 211 3. Length of Pipe 1101 <br />4. Burial Depth of Leak Detector. 22'1 S. Kind of Fuel: 87 6. Date of Last Test: 2012 <br />Test Conditions <br />1. Operating Pump Pressure: 28 PSI 2. Gallon per hour test rate:_3 X10 psi <br />3. Static Line Pressure (Pump Off): 11 PSI 4. Bleed back Test (Pump Off): 75 ml <br />5. Step -Through time to full Flow 5 seconds (0 psi to full pump pressure, no leak) <br />6. Leak detector stays in Leak Search Position with a 3 GPH leak -Yes: X PASS NO:_FAIL <br />7. Was the leak detector adjusted - Yes: No: <br />Symptoms <br />1. Won't find 3 GPH <br />3. Other: <br />2. Stays in Slow <br />9 d d":: 09L 6ZAsW <br />