Laserfiche WebLink
06a <br /> A 53/A 53M - <br /> 12.2 Surface imperfections that penetrate more than 12.5 % 13.2 The number of flattening tests for electric-resistance- <br /> of the specified wall thickness or encroach on the minimum welded pipe shall be in accordance with 7.3.3.2 or 7.3.3.3, <br /> wall thickness shall be considered defects. Pipe with defects whichever is applicable. <br /> shall be given one or more of the following dispositions: 13.3 Except as allowed by 9.2, each length of pipe shall be <br /> 12.2.1 The defect shall be removed by grinding, provided subjected to the hydrostatic test (see Section 8). <br /> that the remaining wall thickness is within specified limits, <br /> 12.2.2 Type S pipe and the parent metal of Type E pipe, 14. Retests <br /> except within 'h in. [13 mm] of the fusion line of the 14.1 Except for flattening tests of electric-resistance-welded <br /> electric-resistance-weld seam, are permitted to be repaired in pipe, if the results of a mechanical test for a lot fail to conform <br /> accordance with the welding provisions of 12.5. Repair weld- to the applicable requirements specified in Section 7, the lot <br /> ing of Type F pipe and the weld seam of Type E pipe is shall be rejected unless tests of additional pipe from the <br /> prohibited. affected lot of double the number originally tested are subse- <br /> 12.2.3 The section of pipe containing the defect shall be cut quendy made and each such test conforms to the specified <br /> off within the limits of requirement on length, or requirements.Only one retest of any lot will be permitted.Any <br /> 12.2.4 Rejected. individual length of pipe that conforms to the test requirements <br /> 12.3 At the purchaser's discretion,pipe shall be subjected to is acceptable. Any individual length of pipe that does not <br /> rejection if surface defects repaired in accordance with 12.2 are conform to the test requirements may be resubmitted for test <br /> not scattered,but appear over a large area in excess of what is and will be considered acceptable if tests taken from each pipe <br /> considered a workmanlike finish.Disposition of such pipe shall end conform to the specified requirements. <br /> be a matter of agreement between the manufacturer and the 14.2 Electric-Resistance-Welded Pipe Produced in Single <br /> purchaser. Lengths-If any flattening test result fails to conform to the <br /> 12.4 For the removal of imperfections and defects by requirements specified in 7.3.3,the affected single length shall <br /> grinding,a smooth curved surface shall be maintained,and the be rejected unless the failed end is subsequently retested using <br /> wall thickness shall not be decreased below that permitted by the same weld orientation as the failed test and a satisfactory <br /> this specification.It shall be permissible to reduce the outside test result is obtained before the pipe's length is reduced by <br /> diameter at the point of grinding by the amount so removed. such testing to less than 80% of its length after the initial <br /> 12.4.1 Wall thickness measurements shall be made with a cropping. <br /> mechanical caliper or with a properly calibrated nondestructive 14.3 Electric-Resistance-Welded Pipe Produced in Multiple <br /> testing device of appropriate accuracy. In the case of a dispute, Lengths-If any flattening test result fails to conform to the <br /> the measurement determined by use of the mechanical caliper requirements specified in 7.3.3, the affected multiple length <br /> shall govern. shall be rejected or flattening tests shall be made using a test <br /> 12.5 Weld repair shall only be permitted with the approval specimen taken from each end of each individual length in the <br /> of the purchaser and in accordance with Specification A.5301 failed multiple length. For each pipe end, such tests shall be <br /> A 530M. made with the weld alternately at 0° and 90° from the line of <br /> 12.6 The finished pipe shall be reasonably straight. direction of force.Individual lengths are considered acceptable <br /> 12.7 The pipe shall contain no dents greater than 10% of if the test results for both pipe ends conform to the specified <br /> the pipe diameter or '/4 in. [6 mm], whichever is smaller, requirements. <br /> measured as the gap between the lowest point of the dent and 15. Test Methods <br /> a prolongation of the original contour of the pipe.Cold-formed <br /> dents deeper than'/in.[3 mm]shall be free of sharp-bottomed 15.1 The test specimens and the tests required by this <br /> gouges; it shall be permissible to remove the gouges by specification shall conform to those described in the latest issue <br /> grinding, provided that the remaining wall thickness is within of Test Methods and Definitions A 370. <br /> specified limits. The length of the dent in any direction shall 15.2 Each longitudinal tension test specimen shall be taken <br /> not exceed one half the specified outside diameter of the pipe. from a pipe end and shall not be flattened between the gage <br /> marks. <br /> 13. Number of Tests 15.3 Test specimens for bend tests and flattening tests shall <br /> 13.1 Except as required by 13.2, one of each of the tests be taken from pipe.Test specimens for flattening tests shall be <br /> specified in Section 7 shall be made on test specimens taken smooth on the ends and free from burrs. <br /> from one length of pipe from each lot of each pipe size. For 15.4 Tests shall be conducted at room temperature. <br /> continuous-welded pipe,each tot shall contain no more than 25 <br /> tons [23 Mg] of pipe for pipe sizes NPS 1'/•- [DN 401 and 16. Lengths <br /> smaller, and no more than 50 tons [45 Mgt of pipe for pipe 16.1 Unless otherwise specified, pipe lengths shall be in <br /> sizes larger than NPS 1'/ [DN 401. For seamless and electric- accordance with the following regular practices: <br /> resistance-welded pipe, a lot shall contain no more than one 16.1.1 Except as allowed by 16.1.2 and 16.1.4,pipe lighter <br /> heat, and at the option of the manufacturer shall contain no than extra-strong weight shall be in single-random lengths of <br /> more than 500 lengths of pipe (as initially cut after the final 16 to 22 ft[4.88 to 6.71 m],with not more than 5 %of the total <br /> pipe-forming operation, prior to any further cutting to the number of threaded lengths furnished being jointers (two <br /> required ordered lengths) or 50 tons [45 Mg] of pipe. pieces coupled together). <br /> 7 <br />