0 <br /> 4, TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer Z Industry Standard ❑ Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ®Vacuum ❑Hydrostatic <br /> ❑Other(Spec6) <br /> Test Equipment Used: VACUUM GAUGE Equipment Resolution:0.5" <br /> r, - <br /> Tankli87 Tank#89 Tank#91 Tank# <br /> Is Tank Exempt From Testing^' ❑ Yes ®No ❑Yes ®No ❑Yes S No ❑Yes ❑No <br /> Tank Capacity: 19309 11608 10161 <br /> Tank Material: FG FG FG <br /> Tank Manufacturer: UNK UNK UNK <br /> - - <br /> Product Stored; 87 89 91 - <br /> Wait time between applying <br /> pressure/vacuum/water and 5 MIN 5 MIN 5 MIN <br /> starting test: ---- <br /> Test Start Time: 10:30 10:30 10:30 <br /> Initial Reading(R,): -10" 10" 10" -- ---------------_ <br /> Test End Time: 11:30 11:30 — — 11:30 <br /> 10' -to"- <br /> to" _ -10" <br /> Final Reading(ftF): __._._......-- __-- <br /> Test Duration: 1 IiR 1 FIR I FIR <br /> Change in Reading(RF-Ri): 0 0 0 <br /> Pass.Fail Threshold or Criteria: 0 0 0 <br /> Test Result: Pass ❑Fail ® Pass ❑ Fails OrPass ❑ Feil { Pass ❑ Fail, <br /> Was sensor removed for testing? ❑Yes®No❑NA ❑Yes®No❑NA ❑Yes®No❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and ❑Yes❑No®NA ❑Yes❑No®NA ❑Yes❑No®NA ❑Yes❑No❑NA <br /> verified functional after testing? <br /> Comments-(include information on repairs made prior to testing and recommended follow-up for jailed felts) <br /> i- tC iVE-c <br /> NOV 2 5 2014 <br /> [ENVIRONMENTAL <br /> HFO!?U nCDQ OT1ACAt�• <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code of Regulations,Title 23.Section 2637(a)(6)} <br /> Secondary Containment Test Results 2 of 6 <br />