Page 1 of 3 <br /> PILUOVERFILL CONTAINMENT BOXEwr <br /> Facility is Not Equipped With Fill Riser Containment Sumps r <br /> Fill Riser Containment Sumps are Present, but were Not Tested r <br /> Spill Box# Spill Box# Spill Box# <br /> Tank waste oil near Tank waste oil near Tank anti <br /> rack WASTE OIL gate WASTE OIL freeze ANTIFREEZE <br /> Fill-Direct Fill-Direct Fill-Direct <br /> Bucket Diameter: 20.00 20.00 20.00 <br /> Bucket Depth: 14.00 14.00 20.00 <br /> Test Method Developed By: Industry Standard Industry Standard Industry Standard <br /> Test Method Used By Vacuum Vacuum Vacuum <br /> Test Equipment Used: VACUUM TEST VACUUM TEST VACUUM TEST <br /> Equipment Resolution: 0.1 gph 0.1 gph 0.1 gph <br /> Wait time between applying <br /> pressure/vacuum/water and 0 min 0 min 0 min <br /> starting test <br /> Test Start Time: 11:55:00 1241:00 09:41:00 <br /> Initial Reading mo: 30.00 in. H2O 30.00 in. H2O 30.00 in. H2O <br /> Test End Time: 11.56:00 12:42:00 09.42:00 <br /> Final Reading m,t 29.00 in. H2O 29.00 in. H2O 29.00 in. H2O <br /> Test Duration: 1 min 1 min 1 min <br /> Change in Reading m,«d: -1.00 in. H2O -1.00 in. H2O -1.00 in. H2O <br /> Pass/Fail Threshold or Criteria: +/-4.00 +1-4,00 +/-4.00 <br /> Test Result Pass Pass Pass <br /> Comments?(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2309431 <br />