Laserfiche WebLink
Page 2 of 3 <br /> PILLIOVERFILL CONTAINMENT BOXE.. <br /> Facility is Not Equipped With Fill Riser Containment Sumps(— <br /> Fill Riser Containment Sumps are Present, but were Not Tested r <br /> Spill Box# <br /> Spill Box# Spill Box# Tank waste oil tank <br /> Tank gear oil GEAR OIL Tank motor oil MOTOR OIL pad WASTE OIL <br /> Fill-Direct Fill-Direct Fill-Direct <br /> Bucket Diameter: 20.00 20.00 20.00 <br /> Bucket Depth: 20.00 20.00 20.00 <br /> Test Method Developed By: Industry Standard Industry Standard Industry Standard <br /> Test Method Used By: Vacuum Vacuum Vacuum <br /> Test Equipment Used: VACUUM TEST VACUUM TEST VACUUM TEST <br /> Equipment Resolution: 0.1 gph 0.1 gph 0.1 gph <br /> Wait time between applying <br /> pressure/vacuum/water and 0 min 0 min 0 min <br /> starting test <br /> Test Start Time: 09:45:00 0949:00 09:54:00 <br /> Initial Reading ow: 30.00 in. H2O 30.00 in. H2O 30.00 in. H2O <br /> Test End Time: 0946:00 09:50:00 09:5500 <br /> Final Reading 29.00 in. H2O 29.00 in. H2O 29.00 in. H2O <br /> Test Duration: 1 min 1 min 1 min <br /> Change in Reading�rny: -1.00 in. H2O -1.00 in. H2O -1.00 in. H2O <br /> Pass/Fail Threshold or Criteria: +/-4.00 +/-4.00 +/-4.00 <br /> Test Result: Pass Pass Pass <br /> Comments?(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> I <br /> I <br /> WO.2309431 <br />