Laserfiche WebLink
Page 3 of 3 <br /> PILL/OVERFILL CONTAINMENT BOXE' <br /> Facility is Not Equipped With Fill Riser Containment Sumps r <br /> Fill Riser Containment Sumps are Present, but were Not Tested r <br /> Spill Box# <br /> Tank wash solvent WASH Spill Box# Spill Box# <br /> SOLVENT <br /> Fill-Direct <br /> Bucket Diameter: 20.00 <br /> Bucket Depth: 14.00 <br /> Test Method Developed By: Industry Standard <br /> Test Method Used By: Vacuum <br /> Test Equipment Used: VACUUM TEST <br /> Equipment Resolution: 0.1 gph <br /> Wait time between applying <br /> pressure/vacuum/water and 0 min min min <br /> starting test <br /> Test Start Time: 10:39:00 <br /> Initial Reading my: 30.00 in.H2O <br /> Test End Time: 10:40:00 <br /> Final Reading ma: 30.00 in. H2O <br /> Test Duration: 1 min <br /> Change in Reading mi,+ 0.00 in. H2O <br /> Pass/Fail Threshold or Criteria: +/-4.00 +/- +/- <br /> Test Result: Pass <br /> Comments 9(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2309431 <br />