Item 318: The line leak detector was adjusted and passed the test on 8/8/16.This violation has been corrected. <br /> Item 320: The EHD was informed on August 8, 2016 that automatic tank gauges (ATG) are used for overfill protection on <br /> both the auto and truck sides of the facility.The ATGs were tested and passed. <br /> Violation, Item 305, still needs to be addressed. Interstitial communication has not been tested and verified for vacuum <br /> sensor monitoring of the secondary containment piping of the truck side of the facility and the 87-, 91, and diesel- <br /> product vent lines on the auto side of the facility. What is being done to correct this violation? <br /> Please respond to the items listed above. <br /> Thank you. <br /> Vicki McCartney, Senior REHS <br /> San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue <br /> Stockton, California 95205 <br /> Phone: (209) 468-9852 <br /> Email: ymccartney Q_sjcehd.com <br /> o `1 <br /> From: Sharlene Woods [mailto:sharlene@bggroupinc.com] <br /> Sent: Thursday, October 20, 2016 6:12 PM <br /> To: Vicki McCartney [EH] <br /> Subject: Fast Lane Central Valley Update <br /> Ms. McCartney, <br /> Please see attached update to the original report. I understand remedy dates <br /> are needed. Supporting documentation will be sent in one packet. <br /> Action Requested: <br /> Brian Dunahay of Epic Compliance requested your guidance. Please reference <br /> his email in Item #207 of the attached document. <br /> I am continuing to work on securing soled reference files for all items. Thank <br /> you in advance for your time. <br /> Regards, <br /> 2 <br />