San Joaquin County
<br /> Environmental Health Department
<br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232
<br /> Telephone: (209)468-3420 Fax: (209) 468-3433 Web:www.sgov.org/ehd
<br /> Underground Storage Tank Program Inspection Report
<br /> Facility Name: Facility Address: Date.
<br /> Fast Lane Central Valley 116 Roth Rd, Lathrop August 08, 2016
<br /> SUMMARY OF VIOLATIONS
<br /> (CLASS I,CLASS II,or MINOR-Notice to Comply)
<br /> Item# Remarks
<br /> 316 HSC 25290.1(c3), 25290.2(c3) Secondary containment not constructed to prevent water intrusion (after Jul 2003).
<br /> Water was found in the diesel north submersible turbine pump (STP) sump, diesel south STP sump, under dispenser
<br /> containment(UDC) sumps for UDC 131146, UDC 14A/15B, UDC 15A/16B, UDC 16A/17B, UDC 17A/18B, and UDC
<br /> 18A/19 on the truck side of the facility. Secondary containment shall be constructed to prevent any water intrusion
<br /> into the system by precipitation, infiltration, or surface runoff. The service technician removed approximately:
<br /> one-half cup of liquid from UDC 13/14B, one cup of liquid from UDC 14A11 5B, one-half cup of liquid from UDC
<br /> 15A/16B, one-and-a-half cups of liquid from UDC 16A/17B, one cup of liquid from UDC 17A/18B and one cup of
<br /> liquid from UDC 18A/19 and returned the sensors to their proper locations. Note that liquid was found in UDCs:
<br /> 13/14B, 16A/17B, 17A/18B and 18A/19 during the inspection on June 17, 2016. Immediately contact a properly
<br /> licensed, trained, and certified contractor to address the water intrusion into the STP and UDC sumps under permit
<br /> and inspection of the Environmental Health Department.
<br /> This is a repeat violation, Class II.
<br /> 318 CCR 2636(f)(2) Leak detector failed to detect a 3.0 gph leak at 10 psi.
<br /> The south diesel (D1) underground storage tank VMI line leak detector on the truck side of the facility failed to detect
<br /> a leak when tested on 8/8/2016. The service technician stated that a new siphon jet valve had been installed on
<br /> 6/16/2016. All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. The service
<br /> technician adjusted the leak detector, retested it, and it passed.
<br /> This was corrected on site.
<br /> This is a repeat violation, Class ll.
<br /> 319 CCR 2635(b) No spill bucket, failed to contain five gallons, or failed to provide a means to keep it empty.
<br /> Approximately one cup of liquid was found in the south diesel spill container on the truck side of the facility and
<br /> approximately two cups of liquid were found in the diesel spill container on the auto side of the facility. Spill
<br /> containers shall be constructed to prevent any liquid retention. Note that fuel was found in the south diesel spill
<br /> container during the inspection on June 17, 2016. Continue to monitor for liquid in the spill containers and remove
<br /> the liquid when present.
<br /> This is a repeat violation, Class II.
<br /> Overall Inspection Comments:
<br /> An inspection checklist was provided to the facility operator on the day of continuation of the monitoring system
<br /> certification inspection performed on August 8, 2016. The Environmental Health Department (EHD) completed th4
<br /> amended written report on September 1, 2016, which replaced the checklist left at the facility, and emailed the
<br /> amended report, along with the checklist completed on August 8, 2016 and photos taken on August 8, 2016, to
<br /> Hardeep Gill, environmental contact. The September 1, 2016 inspection report for the August 8, 2016 testing was
<br /> amended again by the EHD on September 8, 2016, by revising violation 319. The EHD has amended for a third
<br /> time the inspection report for testing performed on August 8, 2016. The revision includes removing violation 313.
<br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement
<br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting
<br /> Page 4 of 5