Installation Instructions <br /> Pre-Installation <br /> Before installation of the TC-3000 Leak Detection System begins, it should be first determined that <br /> the proper cable lengths have been specified and delivered. It is necessary that all applicable elec- <br /> trical standards be followed, and to comply with the electrical and safety code having jurisdiction in <br /> the local area. <br /> Monitor Location <br /> The monitor should be mounted in a readily accessible location where power is available and alarm <br /> lights are clearly visible. Secure the cabinet by screws or bolts through the mounting slots to a perma- <br /> nent position, free from vibration and away from extremely hazardous areas. <br /> Conduit Installation <br /> A conduit system is recommended to protect the ~Gap <br /> cables between monitoring stations. All conduit <br /> should be 11/2". Connections are made at the <br /> monitoring well using a 3" to 11/2" Cross Fitting <br /> (Illustration 1). The cross fitting should be <br /> covered by a "cable access manhole." (Cross UJLL <br /> Fittings are supplied with Tank Jackets only.) <br /> Conduit <br /> Cross FittingIllustration 1 <br /> 1. Run 11/2" conduit from the monitor to the first monitoring station and connect it into the cross <br /> fitting. (Slow Bends should be used to avoid 900 or 450 fittings.) <br /> 2. Run conduit from the first monitoring station to the second and so on. - <br /> 3. All conduit connections should be water-tight. <br /> 4. Before any cable is installed, the conduit system should be complete and backfilled. <br /> —9— <br />