Laserfiche WebLink
• • RECEIVED <br />SWRCB, January 2002 NOV 14e=of <br />.w1i, AlTXTiii AD TVQTV%TV- FNVIR0NMFNTAI HFAITH <br />Test Method Developed By: X Tank Manufacturer ❑ Industry Standard ❑ Profes ARWENT <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure X Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. <br />Tank # 1&2 Tank # <br />Is Tank Exempt From Testing?' No <br />Equipment Resolution: -'/�" x -301-1g. <br />Tank it Tank # <br />Tank Capacity: <br />20K Split 12/8 <br />Tank Material: <br />Fiberglass <br />Tank Manufacturer: <br />XERXES <br />Product Stored: <br />Regular 87/Super 91 <br />Wait time between applying <br />vacuum and starting test: <br />30 Minutes <br />Test Start Time: <br />9:30 <br />Initial Reading (R,): <br />-10 Hg. <br />Test End Time: <br />11:30 <br />Final Reading (RF): <br />-10 Hg. <br />Test Duration: <br />2 Hours <br />Change in Reading (RF -R,): <br />0 Hg. <br />Pass/Fail Threshold or Criteria: <br />➢ -2 Hg. <br />Test Result: <br />Pass <br />Was sensor removed for testing? <br />No <br />Was sensor properly replaced and <br />verified functional after testing? <br />N/A <br />Comments (include information on repairs made prior to testing and recommended follow-up for failed tests) <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />