My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2016-2018
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
L
>
LODI
>
2500
>
2300 - Underground Storage Tank Program
>
PR0231356
>
COMPLIANCE INFO_2016-2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/7/2022 10:55:27 AM
Creation date
11/8/2018 9:36:46 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2016-2018
RECORD_ID
PR0231356
PE
2361
FACILITY_ID
FA0003815
FACILITY_NAME
TESORO (MOBIL) 68154
STREET_NUMBER
2500
Direction
W
STREET_NAME
LODI
STREET_TYPE
AVE
City
LODI
Zip
95240
APN
02740006
CURRENT_STATUS
01
SITE_LOCATION
2500 W LODI AVE
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Supplemental fields
FilePath
\MIGRATIONS3\L\LODI\2500\PR0231356\COMPLIANCE INFO.PDF
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
283
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer ®Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑Pressure ❑ vacuum ®Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: ancon Sump Tester Equipment Resolution: +1-0.002" <br /> UDC#1/2 UDC#3/4 UDC#5/6 UDC#11/12 <br /> UDC Manufacturer: Environ Environ Environ Environ <br /> UDC Material: Green Plastic Green Plastic Green Plastic Plastic <br /> UDC Depth: 31" 31" 31" 31" <br /> Height from UDC Bottom to Top 7" 7" 7" T' <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 4„ 4„ 4" 4" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Good Good Good Good <br /> testing: <br /> Portion of UDC Tested 2"above piping 2"above pipe* 2"above piping 2"above piping <br /> Does turbine shut down when <br /> UDC sensor detectsliquid(both ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA <br /> product and water)? <br /> Turbine shutdown response time N/A N/A N/A N/A <br /> Is system programmed for fail- ❑yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA <br /> safe shutdown?' <br /> Was fail-safe verified to be ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes 30 minutes 30 minutes 30 minutes <br /> starting test <br /> Test Start Time: 2:23 put 1:54 pm 12:31 pm 12:31 pm <br /> Initial Reading(RI): 5.7177 6.7379 2.1474 3.5743 <br /> Test End Time: 2:38 pm 2:09 pin 12:46 pro 12:46 pin <br /> Final Reading(RF): 5.7176 6.7374 2,1476 3.5749 <br /> Test Duration: 15 min. 15 min. 15 min. 15 min. <br /> Chan a in Reading(RF-R j): 0.0001 0.0005 0.0002 0.0006 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" +/-0.002" +/-0.002" <br /> Test Result: ® Pass ❑Fail M Pass ❑Fail ® Pass ❑Fail 011 Pass ❑Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA N Yes❑No❑NA ®Yes❑No❑NA ®Yes❑No❑NA <br /> Was sensor properly replaced and ®Yes❑No ❑NA ®Yes❑No❑NA ®Yes❑No❑NA ®Yes❑No❑NA <br /> verified functional after testis ? <br /> Comments—(include information on repairs made prior to testing and recommended follow-up far failed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> Readjusted jumper lines in UDC's 1/2, 3/4, 5/6, & 11/12. n C t%C <br /> ri I V 15 ems+ <br /> -co ice^ 917 <br /> TAI UE:AITN <br /> - rlvin T <br /> rTT YH <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested. If the answer to gU of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />
The URL can be used to link to this page
Your browser does not support the video tag.