Laserfiche WebLink
b• All monitoring probe inputs shall be Belden 8448 if length of <br /> a' run equals 0 to 1,000 ft. If length <br /> 2,500 ft., Belden 9182 cable shall be used. run equals 1,000 to <br /> c. All auxiliary input wire shall be 18 gauge, TM N, shielded <br /> wire. <br /> d. Auxiliary output wire shall <br /> allow for proper operation of be of sufficient size and <br /> end devices. <br /> type to <br /> 4. Horn - An audible horn shall be furnished, installed and tested <br /> fi <br /> withallnecessary wire and terminations for a complete, operating <br /> s'` ocated at grids A-5 in the warehbuse. A `silence button, <br /> which automatically resets when the alarm condition clears shall <br /> be located at grids A-5 in the warehouse. <br /> The horn shall be a Federal Vibratone Horn, Model 450, 24 VDC, wB <br /> location shall bdesignated <br /> or approved alternate. The <br /> suras face <br /> be run in conduit. meted on the drawings. All wire shall <br /> 5. fight - A small 24 VDC red LED <br /> provided to type indicating light shall be <br /> indicate an l <br /> alarm condition. This light shall <br /> automatically extinguish upon the clearance of the alarm condition <br /> and shall not be affected by the silence button. <br /> Nom: The light and silence button shall be mounted in the tank <br /> monitor panel cover so as to be readily visible. <br /> N. Tank and piping installation shall be supervised by the tank manufac- <br /> startturer's representative and monitoring equipment installation and <br /> start-up shall be by the monitoring equipment manufa <br /> -up service representative. cturer's author- <br />