7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer M Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: INCON SUMP TESTER Equipment Resolution:0.002" <br /> UDC#7-8 UDC#9-10 UDC# UDC# <br /> UDC Manufacturer: Bendel Bendel <br /> UDC Material: Fiberglass Fiberglass <br /> 77 <br /> UDC De the 34" 34" <br /> Height from UDC Bottom to Top 12„ 12" <br /> of Highest Pi in Penetration: <br /> Height from UDC Bottom to 14„ 14" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry <br /> testing: <br /> Portion of UDC Tested' 27 Penetrations 2"I Penetrations <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No N NA []Yes ❑No ®NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> product and water)?* <br /> Turbine shutdown response time NIA NIA <br /> Is system programmed for fail- ❑Yes ❑No E NA ❑Yes [:]No M NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> safe shutdown?* <br /> Was fail-safe verified to be ❑Yes [-]No ENA ❑Yes ❑No M NA ❑Yes ❑No ❑NA [-]Yes ❑No ❑NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min 10 min <br /> startin test <br /> Test Start Time: 11:10am 11:46am <br /> Initial Readin RI): 5.7515" 6.9073" <br /> Test End Time: 11:25am 12:01 pm <br /> Final Readin (RF): 5.7515" 6.9067" <br /> Test Duration: 15min 15min <br /> Chan a in Readin RF-R,): 0.000" -0.0006" <br /> Pass/Fail Threshold or Criteria: +l-0.002" +l-0.002" +l-0.002" +l-0.002" <br /> Test Result: ® Pass ❑ Fail E Pass E] ail ❑ Pass ❑ Fail ❑Pass ❑ Fail <br /> Was sensor removed for testing? E Yes ❑No ❑NA E Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and M Yes ❑No ❑NA M Yes ❑No ❑NA [--]Yes ❑No [INA ❑Yes ❑No ❑NA <br /> verified functional after testing" <br /> Comments (include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE TESTS <br /> ENVY` <br /> ' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />