Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Phillips Facility <br /> Tank #: 1 Test Date: 6/24/02 <br /> Product: Unleaded Regular Work#: 7405890 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Vaporless <br /> Diameter(in): LID Model: LD2000 <br /> Product Level(in): L/D Serial#: 68090 <br /> Liquid Volume(Gals): Line Drain Back(ml): 85 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 28 <br /> Coef.of Expansion: Metering Pressure(psi): 18 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector! No <br /> Head Pressure(psi): it <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket j <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> ULLAGE TEST RESCLTLine Start Time: 10:48:00 AM <br /> Test Method: ULLAGE Line End Time: 11:03:00 AM <br /> UllageVolume(gals.): Line Start Level: 235 <br /> Ullage Test Time: Line End Level: 240 <br /> Ullage Vacuum(psi): Line Test Rats(gph): 0.005 <br /> Ullage Result: N/A Line Test Result: PASS <br /> COMMENTi <br /> 2 <br />