Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Phillips Facility <br /> Tank #: 2 Test Date: 6/24/02 <br /> Product: Unleaded Premium Work#: 7405890 <br /> TANK IESf RESULI LEAKDETECPOR IK RESULT. ., <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: FE Petro <br /> Diameter(in): L/D Model: FE <br /> Product Level(in): L/D Serial#: 01101219 <br /> Liquid Volume(Gals): Line Drain Back(ml): 110 <br /> Liquid Percent(%): L/D Trip Time(sec): 14 <br /> Specific Gravity: Holding Pressure(psi): 12 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? Yes <br /> Head Pressure(psi): �PI��I',l �� <br /> Test Start Time. <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): <br /> Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> -- ------------ - -- Line Pressure(psi): 50 <br /> m � <br /> UILmRESULT Line Start Time: 10:48:00 AM <br /> Test Method: ULLAGE Line End Time: 11:03:00 AM <br /> UllageVolume(gals.): Line Start Level: 255 <br /> Utlage Test Time: Line End Level: 260 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.005 <br /> j Line Test Result: PASS j - <br /> Ullage Result: N/A <br /> COMMENTS . <br /> 3 <br />