Laserfiche WebLink
Triangle Environmental Inc <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 01205 <br /> Tank #: 1 Test Date: 7/16/2001 <br /> Product: Unleaded Regular Work#: 7405410 <br /> TEST RESULT LEAK DETECTOR TEST RESULT <br /> Test Method: Test Method: R.J. FTA <br /> Capacity: 11849 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 68085- <br /> Liquid <br /> 8085_Liquid Volume(Gals): Line Drain Back(ml): 45 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 30 <br /> Coef. of Expansion: Metering Pressure(psi): 22 <br /> Water On Tank(in): L/D Test Rate(gph): 0.8 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): •_- - T - <br /> LINE TEST RESULT <br /> Test Start Time: - <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> ULLAGE TEST RESULT Line Pressure (psi): <br /> Line Start Time: 3:3:05:00 PM <br /> Test Method: ULLAGE Line End Time: 3:20:00 PNI <br /> Ullage Volume(gals.): Line Start Level: 295 <br /> Ullage Test Time: Line End Level: 300 <br /> Ullage Vacuum(psi): Line Test Rate (gph): 0.000 <br /> Ullage Result: N/A Line Test Result: PASS <br /> I4 it Cm <br /> 2 <br />