Laserfiche WebLink
Triangle Environmental Inc <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 01205 <br /> Tank #: 2 Test Date: 7/16/2001 <br /> Product: Unleaded Premium Work#: 7405410 <br /> TANK TEST RESULT LEA�f77ETE�TOI�TEST RESULT:,' <br /> Test Method: Test Method: R.J. FTA <br /> Capacity: 11849 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 60892 <br /> Liquid Volume(Gals): Line Drain Back(ml): 55 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 30 <br /> Coef.of Expansion: Metering Pressure(psi): 20 <br /> Water On Tank(in): L/D Test Rate(gph): 1.3 <br /> Water In Tank(in): L/D Result PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): egg ,a . : u , �� <br /> Test Start Time: ,a _Maw LT <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> -- -- - — -- Line Pressure(psi): 50 <br /> ULLAGE TEST RESULT Line Start Time: 3:05:00 PM <br /> Test Method: ULLAGE Line End Time: 3:20:00 PM <br /> Ullage Volume(gals.): Line Start Level: 210 <br /> Ullage Test Time: Line End Level: 210 <br /> Line Test Rate(gph): 0.000 <br /> Ullage Vacuum(psi): <br /> Ullage Result: N/A Line Test Result: PASS <br /> COMMENTS <br /> 3 <br />