Laserfiche WebLink
Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMARYSHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Tosco Marketing Co. TOSCO Facility # 30225 <br /> 3550 North Central Avenue <br /> Phoenix, AZ 85012- Test Date 6/ 2/98 <br /> Carmen Tucker <br /> (602)200-4530 <br /> Facility: '� Work#: 460340 <br /> Tosco Facility # 30225 1 County: SAN JOAQUIN <br /> 16500 � Cross Street: SEQ LOUISE&I-5 <br /> LATHRUP, CA 95209 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Reault L/D Result <br /> 1 Unleaded Plus 7632 System 5000 0.010 PASS PASS 0.000 PASS PASS <br /> 2 Unleaded Premium 5737 System 5000 0.010 PASS PASS 0.000 PASS PASS <br /> 3 Unleaded Regular 9528 System 5000 0.010 PASS PASS -0.011 PASS PASS <br /> ce id"d Isy. Technician: James Bowen State Lie.#s: CA-97-1603 <br /> P -;;7 <br /> Mfgr's#: TEI-053 IFCI-98212 AZ-T00033 <br /> ° ID-9634006 CO-0547A <br /> Comments: <br /> Compliance test ALL <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA. <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5%as required by Local,State and Federal EPA UST Technical Standards <br /> Part 280 for precision testing systems. <br />