Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 30225 <br /> Tank #: 1 Test Date: 6/ 2/98 <br /> Product: Unleaded Plus Work#: 460340 <br /> TANK TEST RESULT LEAK DETECTOR TEST ULT <br /> Test Method: System 5000 Test Method: R.J. FTA <br /> Capacity: 7632 Manufacturer: Vaporless <br /> Diameter(in): 91 L/D Model: LD2000 <br /> Product Level(in): 58 L/D Serial#: 46018 <br /> Liquid Volume(Gals): 5137 Line Drain Back(ml): 100 <br /> Liquid Percent(%): 67.3% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 26 <br /> Coef. of Expansion: 0.000650 Metering Pressure(psi): 22 <br /> Water On Tank(in): 40 L/D Test Rate(gph): 1.7 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 70 New Leak Detector? No <br /> Head Pressure(psi): 0.1 <br /> Test Start Time: 7:00 PM <br /> Test End Time: 7:20 PM Test Method: TEl LT-3 <br /> Test Rate(gph): 0.010 Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> ULLAGE TEST RESULT Line Start Time: 10:15 PM <br /> Tcst MethodULL4(iC Line End Time: 10:30 PM <br /> : <br /> UllageVolume(gals.): 2495 <br /> Line Start Level: 170 <br /> Ullage Test Time: 7:00 PM <br /> Line End Level: 170 <br /> Ullage Vacuum(psi): 0.6 <br /> Line Test Rate(gph): 0.000 <br /> Ullage Result: PASS <br /> Line Test Result: PASS <br /> 2 <br />