Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> WorkOrder #: D1395 Test Date: 10/29/95 <br /> Facility: CIRCLE K #1205 <br /> Tank ID#: 1 Product: UNLEADED Capacity: 10000 <br /> Test Method: TEI System 4000 Test Method: R.J.FTA <br /> Diameter(in): 95 Manufacturer: Red Jacket <br /> Product Level(in): 125 L/D Model: DLD <br /> Liquid Volume(Gals): 10000 L/D Serial#: 10690-1119 <br /> Liquid Percent(%): 100.0% Line Drain Back(ml): 310 <br /> Specific Gravity: 0.750 L/D Trip Time(sec): 2 <br /> Coef. of Expansion: 0.000657 Holding Pressure(psi): 10 <br /> Water On Tank(in): 0 Metering Pressure(psi): I I <br /> Product Temp. (F): 74.90 L/D Test Rate(gph): 160 <br /> Head Pressure(psi): 3.4 L/D Result: PASS <br /> Test Start Time: 10:00:00 PM q x. Q. ..3i.,,,,., <br /> g <br /> Test End Time: 4:00:00 AM :��3;.> . .:..._...,.:>:`..:..,.:..:,�.:�::,.,.::a„ r <br /> Test Rate(gph): 0.001 Test Method: TEI LT-3 <br /> Test Result: PASS Pump Brand: Red Jacket <br /> r: <br /> System Type: Pressure <br /> ` <br /> Line Pre <br /> nsure(psi): <br /> Test Method: TEI ULLAGE Line Start Time: 1:40:00 AM <br /> UllageVolume(gals.): 0 Line End Time: 1:55:00 AM <br /> Ullage Test Time: Line Start Level(ml): 290 <br /> Ullage Vacuum(psi): Line End Level(ml): 285 <br /> Ullage Result: N/A Line Test Rate(gph): 0.005 <br /> Line Test Result: PASS <br /> <`.�.....`RJ."' A..xx„n�^'.vi✓i,..>n.ue ..bjf>' : x.^3?li:�. h 4`x�... x... .�v�. <br /> 2 <br />