Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> WorkOrder #• D1395 Test Date: 10/29/95 <br /> Facility: CIRCLE K #1205 <br /> Tank ID#: 2 Product: UNL PLUS Capacity: 10000 <br /> .I'u>'� >'b Y`::. •. Nq\,i :::F:'}n%�";,n :>i;S`:ij :y�>.ii <br /> Test Method: TEI System 4000 Test Method: RJ.FTA <br /> Diameter(in): 95 Manufacturer: Red Jacket <br /> Product Level(in): 117 L/D Model: DLD <br /> Liquid Volume(Gals): 10000 L/D Serial#: 21289-9487 <br /> Liquid Percent(%): 100.0% Line Drain Back(ml): 120 <br /> Specific Gravity: 0.730 L/D Trip Time(sec): 2 <br /> Coef. of Expansion: 0.000681 Holding Pressure(psi): 12 <br /> Water On Tank(in): 0 Metering Pressure(psi): 9 <br /> Product Temp. (F): 78.73 L/D Test Rate(gph): 180 <br /> Head Pressure(psi): 3.1 L/D Result: PASS <br /> Test Start Time: 10:00:00 PM a'` •.., s;.. =s.»«:.as.x f.> <br /> m <br /> Test End Time: 4:00:00 AM <br /> Test Rate(gph): 0.034 Test Method: TEI LT-3 <br /> Test Result: PASS Pump Brand: Red Jacket <br /> System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Test Method: TEI ULLAGE Line Start Time: 1:20:00 AM <br /> UllageVolume(gals.): 0 Line End Time: 1:35:00 AM <br /> Ullage Test Time: Lire Start Level(ml): 350 <br /> Ullage Vacuum(psi): <br /> Line End Level(ml): 340 <br /> Line Test Rate(gph): 0.010 <br /> Ullage Result N/A Line Test Result: PASS <br /> <: <br /> 3 <br />