Laserfiche WebLink
Installation and Maintenance Manual <br /> CNI Manufacturing Phase I Vapor Recovery System Page 22 of 28 <br /> Figure E-1 <br /> Emco Wheaton Fill Adapter <br /> EMCU " A0030-124 <br /> WHEATON RETAIL Swivel Fill Adapter <br /> INSTALLATION INSTRUCTIONS <br /> AGM-124 <br /> i <br /> Swivel Fill <br /> Adapter <br /> Use a <br /> Set Screw -- I �_. <br /> Joist of 2) Flat Gasket <br /> pJn 469828 <br /> i <br /> 3 <br /> p+ { <br /> 1. Using a 5,132"Allen wrench, remove both set screws from the base of the <br /> swivel adapter. <br /> 2. The top edge of the top riser nipple must be filed flat and square,with <br /> threads free of all debris to insure a proper sealing surface between the <br /> riser nipple and the base of the Swivel adapter. <br /> 3. Before installing the swivel adapter,verify that the flat gasket is properly in <br /> place. Manually tighten the swivel adapter on to the top riser nipple td <br /> avoid cross threading. Using the Emco Wheaton Retail A0081 Adapter <br /> Wrench, torque the swivel adapter to 35 ft-lbs. <br /> IMPORTANT., Do not use pipe thread sealantcompound when <br /> Installing the swivel adapter. <br /> 4- Apply lock-tite model#222MS on both set screws. Re-install and torque to <br /> 20 in-lbs- <br />