Laserfiche WebLink
SB Series Pellethane SplitRepair Boots Installation <br /> For Encapsulation Repairs) <br /> STEP I Identify the damaged boot and select the proper Blueline Repair ,. <br /> Boot based upon the number of studs and the pipe OD.(See 2006 <br /> Catalog,Section 10 and Appendix 1) <br /> STEP 2 Install all Pellethane split components onto the pipe carefully.All <br /> s <br /> Pellethane pieces must be rebonded back together with Blue Seal <br /> Glue.This is done by ensuring that the surfaces are clean and dry. <br /> Apply a liberal bead of Blue Seal and hold the seam closed - <br /> securely until it is fused. It's helpful to use the clamps to loosely <br /> hold the boot closed during curing. Bonded connections should f �� <br /> hold themselves closed within five minutes if there are no stresses <br /> on them.The Blue Seal glue will be fully cured in 40 minutes. <br /> STEP Once all Blueline approved components are bonded, apply a <br /> liberal bead of either Parasealant 626, or Bostik IIOOFS to the <br /> underside of the seal.This will make the seal with the sump wall. <br /> Insert poly ring into the gasket and position the ring around the <br /> old fitting and against the sump wall. <br /> STEP 4 Install the self tapping tek screws through the holes in the poly =---------- _ --- <br /> ring and tighten until snug. (Be careful not to over tighten as the <br /> holes can be easily stripped out.) r <br /> STEP 5 Apply a bead of Blue Seal Glue along the gasket rim and install <br /> the boot onto the seal. Install boot with fill tube at the 12,00 iA i <br /> position.Install band clamp to secure the boot to the <br /> gasket.position. 1 ... <br /> BLUELINE TECHNOLOGIES 2001 ■ Fax:[866]31&3848 <br />