Laserfiche WebLink
P.O. BOX 219 <br />NEBRASKA CITY, NE 68410 <br />402-873-4077/800-447-3490 <br />-�� �r�viror�mer�Y-oJ <br />L.L_G_ <br />9595 LUCAS RANCH ROAD, SUITE 100 <br />RANCHO CUCAMONGA, CA 91730 <br />909-476-7443/800-533-4030 <br />ACURITE VOLUMETRIC LINE TEST CERTIFICA <br />Date: 8/8/2005 <br />Location: <br />Yellow Transportation Tracy <br />1535 E. Pescadera Ave. <br />Tracy, CA 95376 <br />Job # T4 027197 <br />Contact: Richard Smith <br />Telephone: 209-833-1573 <br />Test Number <br />1 <br />2 <br />Sum Pum # <br />Line 1 <br />Line 2 <br />Product <br />Diesel <br />Diesel <br />Turbine Manufacturer <br />Big Flow <br />Bi Flow <br />Piping Type <br />DW/ FRP <br />DW/ FRP <br />Piping Manufacturer <br />Smith <br />Smith <br />Piping Length 2" <br />N/A <br />N/A <br />Piping Len th 3" <br />428 Ft <br />428 Ft <br />Isolation (pump) <br />Ball Valve <br />Ball Valve <br />Isolation disp. <br />Ball Valve <br />Ball Valve <br />Test Pressure <br />50 PSI <br />50 PSI <br />Initial Cyl. Level <br />0.95 <br />0.95 <br />Final Cyl. Level <br />0.95 <br />0.95 <br />Begin Time <br />1:30 <br />2:30 <br />End Time <br />2:00 <br />3:00 <br />Change in Time <br />30 Min <br />30 Min <br />Change in Volume <br />0 <br />0 <br />Leak Rate <br />0.005 <br />0.005 <br />Pass / Fail <br />Pass <br />Pass <br />Line Test Method Acurite Acurite <br />Comments: <br />I declare under penalty of perjury that I am a licensed tank tester in the State of California and <br />that the information contained in this report is true and correct to the best of my knowledge. <br />Technician: Paul Magana License # 90-1189 <br />Signature: <br />