Laserfiche WebLink
SWRCB, January 2002 <br />► <br />4. TANK ANNULAR TESTING <br />Page of <br />Test Method Developed By: ❑ Tank Manufacturer X Industry Standard 0 Professional Engineer <br />0 Other (Spec+fy) <br />Test Method Used: 0 Pressure X Vacuum 0 Hydrostatic <br />0 Other (Specify) <br />Test Equipment Used: ESTABROOK <br />GEAR OIL MOTOR OIL <br />Equipment Resolution: 95% <br />USED OEL <br />Is Tank Exempt From Testing?' <br />0 Yes X No <br />0 Yes X No <br />0 Yes X No <br />❑ Yes 0 No <br />Tank Capacity: <br />6,000 <br />10,000 <br />8,000 <br />Tank Material: <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />Tank Manufacturer <br />OWENS <br />OWENS <br />OWENS <br />Product Stored: <br />OIL <br />OIL <br />WASTE OIL <br />Wait time between apphing <br />pressurehacuum/water and <br />starting test: <br />15 MIN <br />15 MIN <br />15 MIN <br />Test Start Time: <br />7:00 <br />7:00 <br />8:15 <br />Initial Reading (R): <br />10.05 HG <br />10.03 HG <br />10.08 HG <br />Test End Time: <br />8:00 <br />8:00 <br />9:15 <br />Final Reading (RI,): <br />10.05 HG <br />10.03 <br />10.08 HG <br />Test Duration: <br />I HR <br />1 HR <br />1 HR <br />Change in Reading (RF Rj): <br />0 <br />0 <br />0 <br />Pass/Fad Threshold or Criteria: <br />0 <br />0 <br />0 <br />Test Resuk: <br />X Pass 0 Fail <br />X Pass 0 Fail <br />X Pass ❑ Fail <br />0 Pass 0 Fail <br />Was sensor removed for testing? <br />X Yes 0 No 0 NA <br />X Yes 0 No 0 NA <br />X Yes 0 No 0 NA❑Yes <br />0 No 0 NA <br />Was sensor operh replaced and <br />verified fitnctitional after testing') IX <br />Yes 0 No 0 NA <br />X Yes []No 0NA <br />X Yes []No 0 NA <br />0 Yes 0 No [INA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for ailed tests) <br />AN77FREEZE, SLOP 4SLOP ZAND SOAP TANK ARE WET ANNULARSARE E%F.MPT FROM TES77NG <br />► <br />► <br />► ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />