Laserfiche WebLink
vp San Joaquin County <br />Environmental Health Department <br />AM LADED <br />1868 East Hazelton Avenue, Stockton, California 95205-6232 <br />Telephone: (209) 468-3420 Fax: (209) 468-3433 Web: www.siaov.org/ehd <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />1 <br />Date: <br />YRC INC <br />1535 E Pescadero Ave, Tracy <br />February 06, 2017 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS ll, or MINOR- Notice to Comply) <br />Item # <br />Remarks <br />110 <br />CCR 2637(e) Failed to submit secondary containment test report within 30 days. <br />Secondary containment testing was performed on 4/27/16 and a test report was submitted on 8/9/16, more than <br />three months late. A copy of the test report must be submitted within 30 days of the tests. Take all necessary <br />precautions to ensure testing and submittal of test reports are performed in a timely manner. <br />This is a minor violation. <br />201 <br />CCR 2712(b) Failed to maintain alarm logs and/or records of follow up actions. <br />The facility did not document and address the T-2 piping sump L5 fuel alarm on January 4, 2017 and the T-4 Gear <br />Oil 6000 Probe Out alarm on February 2, 2017. Monitoring records include: (1) date and time of all monitoring or <br />sampling; (2) monitoring equipment calibration and maintenance records; (3) results of any visual observations; (4) <br />results of sample analysis performed at a lab or in the field; (5) logs of all readings of gauges or other monitoring <br />equipment, ground water elevations, or other test results; (6) results of inventory readings and reconciliations. <br />Going forth, document all alarms on the daily alarm log, and note what action was taken to address the alarms. <br />This is a minor violation. <br />209 <br />CCR 2715(c) Designated operator did not inspect all required items and/or the inspection reports not completed. <br />The designated operator failed to check and note the test date for secondary containment testing on the 8/31/16, <br />9/28/16, 11/30/16, and 1/31/17 designated operator monthly inspection reports. There was no date found on the <br />panel printout for the soap panel associated with the 8/31/16 and 12/29/16 designated operator monthly inspection <br />reports. There was no date found on the panel printouts for the soap panel and panel for the remaining six LISTS <br />associated with the 9/28/16, 10/21/16, and 1/31/17 designated operator monthly inspection reports. The L11 alarm <br />history was missing from the panel printout on 1/31/17; and the L7 and L11 alarm histories were missing from the <br />panel printout on 11/30/16. During the monthly inspection, the designated operator shall check that all required <br />testing and maintenance for the UST system have been completed and document the dates they were done. <br />Ensure that designated operators performing monthly inspections at this facility are including all of the required <br />information on the reports. <br />This is a minor violation. <br />210 <br />CCR 2715(e) Designated operator monthly inspection reports not maintained on site for at least 12 months. <br />The July 2016 designated operator monthly inspection reports for both monitoring panels were not found on site; <br />and the January 2017 designated operator monthly inspection report for the soap monitoring panel was not found on <br />site during the inspection. Designated operator monthly inspection reports for the previous twelve months shall be <br />retained on site. Locate and ensure that copies of the previous twelve months of designated operator monthly <br />inspection reports are maintained on site. Submit copies to the Environmental Health Department (EHD).. <br />This is a minor violation. <br />FA0003854 PR0232495 SCO01 02/06/2017 <br />EHD 23-01 Rev. 09/22/16 Page 4 of 6 Underground Storage Tank Program OIR <br />