Laserfiche WebLink
SAN JOAQUIN COUNTY <br /> ENVIRONMENTAL HEALTH DEPARrMENT <br /> 600 East Main Street, Stockton,California 95202-3029 <br /> Telephone:(209)468.3420 Fax:(209)468-3433 Web:www.siaov.or2Jehd1unitii1tml <br /> CONTINUATION FORM Page: 3 of 5 <br /> OFFICIAL INSPECTION REPORT Date: 05/23/11 <br /> Facility Address: Fast Lane Central 116 East Rath Road, Lathrop Program: UST <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I CLASS It.or MINOR�Notice to Comply) <br /> Required Enforcement Compliance UST Inspection: Monitoring Certification testing Auto and Truck Side <br /> 1. A permk to operate the UST system has not been issued for the 2009, 2010, and 2011 year. No <br /> person may own or operate an UST unless a permit for its operation has been issued by the local <br /> agency to :he owner or operator of the UST system. Immediately obtain a permit to operate a UST <br /> system from the EHD. Contact the EHD accounting department 1'or the permit, An "Operating without a <br /> Permit" penalty applies. `> U,y P((L, L N(o e <br /> 6. A copy of the UST operating permit was not found on site. A copy of the UST operating permit and all <br /> attachments and conditions shall be retained at the facility. Immediately obtain a copy of the permit and <br /> retain it on site. Contact the EHD accounting department for the permit. <br /> 19. The visual light used as part of the overfill prevention system Is not currently functional on the Truck <br /> Side audible/visual UST The light bulb was replaced and retested during the inspection. Passed <br /> functionality test. <br /> 23. Designated operator failed to document all the alarms for the previous month and check that they <br /> were responded to appropriately on the designated operator monthly inspection repport. The missing <br /> alarms not documented on the monthly report include: Auto Side: L9 91 Fill Sump alarm on 02/17/11 at <br /> 2:39PM, Trick Side: L2 Diesel 1 South STP annular on 12/17/10 at 10:12AM, 10:52AM. These two <br /> alarms also lacked a response action. Able Maintenance Work Order 0520756 on 12/17/10 documented <br /> 32 no vac alarm. Able Maintenance invoice 508344 on 09/07/10 documented tank 2 sensor vac- no vac, <br /> Service Station System invoice 113066 on 09/25/10 documented lank 2 sensors - no vac. Work Order <br /> and Invoice alarms were not found on the monthly reports. During the monthly inspection, the <br /> designated operator shall review the alarm history for the previous month, check that each alarm was <br /> documented and responded to appropriately, and attach a copy of the alarm history with documentation <br /> taken in response to any alarms to the monthly report. Ensure that designated operators performing <br /> monthly inspections at this facility are including all of the required information on the eports. <br /> 7. Alarm sensor log was n1 found on site. Any and all afLrms must be recorded by employees if they <br /> were not documented by the Designated Operator. No documentation on alarm logs or monthly reports <br /> can be found for the above alarms referenced in violation d 23. These records shall be kept on site for at <br /> least 3 yearn. Immediately locate maintenance records/work orders and maintain the alarm sensor logs <br /> on site. Worl<orders should be attached to the documented alarms on the Designated Operator's <br /> monthly reports. Submit copies of these maintenance records to EHD associated with the above alarms. <br /> E <br /> EHO STA14 TIME ASSOCIATED WITH FAILING TOCOMPLY BY THE ABOVE NOTED DATESW".L BE BILLED AYTHE CURRENT HOURLY RATE($122). <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHDIS CURRENT HOURLY RATE. <br /> pector: Received By: - 7HIB <br /> , ( <br /> EHO20.0D003 Rey Oan W10 CONTINUATION FORM <br />