FACTS &4IPS
<br /> THAT YOU SHOULD KNOW ABOUT
<br /> PRESSURIZED PIPING LEAK DETECTION
<br /> Detecting leaks in pressurized underground detector tests to be effective the detector must between the fuel and the piping can cause
<br /> piping seems a problem not worthy of the best have a built-in self test mode or scheduled false alarms or hide leaks. In the summer
<br /> of our available engineering talent, right? detector testing will not get done. when fuel is colder than the piping a leak can
<br /> No! Wrong,and here's whv. Consider these Here's a fact you may not know but should. be hidden. That happens because the cold
<br /> conditions: expanding fuel, shrinking fuel, Your line leak detector does not check the fuel expands when it is pumped into the
<br /> air trapped in the pipe,a springy pipe,head underground piping to a satellite nozzle, hotter fuel delivery piping. For this reason
<br /> pressure,just to name the important physical commonly used atdiesel dispensers fortrucks. you could miss a leak.
<br /> conditions.Now,consider that leak detectors Here's another fact you should be aware of; For the above situation a leak detector may
<br /> will be installed in hundreds of different if you have pressurized underground lube not report a leak. Then in the winter months,
<br /> locations, all with different piping arrange- lines,they must be monitored. when fuel is warmer than the pipe, the fuel
<br /> ments. The question must be asked and Don't be alarmed if we have given you tips will shrink and a leak detector may report
<br /> answered,is the leak detector I purchase ca- and facts and you don't know how to solve the falsely a leak.In a third condition,which also
<br /> pable of performing in my particular piping problems posed. We at CAMPO/MILLER can be damaging,is ano test signal.Ifyouget
<br /> configuration,and who decides? Lastly,ifall have the answers,if others do not. a no test signal over a long period of time,you
<br /> of the above are done correctly,who keeps The fact you already know the following, could miss a leak.
<br /> checkon the equipment toverify thatit works, but it is so important we will say it again,your Various procedures are employed by leak
<br /> year after year? Now add to this, the leak biggest exposure is from leaks in pressurized detector manufacturers in determining and
<br /> detector must be installed at a competitive fuel Ripe lines. The reason is simply stated, specifying the line leak detector's perform-
<br /> cost by the low bidder. Do you still think the any leak in pressurized piping is under pres- ance. You can assume the probability of leak
<br /> problem is that easy to solve? If you don't, sure,and therefore the spill through any hole detection or false alarm are correctly stated,
<br /> read on. We have some useful facts and tips size will be larger than a same size hole in a but what you need to know also is what is the
<br /> to pass on to you. tank, whose only pressure is from gravity. probability of a no test signal,from the detec-
<br /> Now,let's deal fust with verifying that the Because of the pressure the continuous 3 gal/ for you have selected because a no test is
<br /> leak detector you purchased and have in- hr test may not give you adequate protection. giving you no data.
<br /> stalled works in yourparticular location.The The reason is a leak detector may not detect a We at CAMPO/MILLER instead of paying
<br /> next important consideration is how will you smaller leak than 3 gal/ltr,which could go on for regular advertising give you this facts and
<br /> verify that it continues to function,for years for months. The .1 gal/hr annual test is tips information,which is intended to inform
<br /> into the future? There is an old saying "To intended to catch those leaks smaller than 3 and advertise our products.
<br /> assume makes a donkey out of U and me." gal/hr. But to wait a year to find such a leak Our line of Electronic Line leak detectors
<br /> Likewise,toassume aline leak detectorworks is too long,with the cost of clean-up as it is! include four models: LS300-120XLC,
<br /> in your location can put your donkey in a We at CAMPO/MILLER have selected the LS300-120, LS-300-120PLUS and LS300-
<br /> sling. The sure way to verify your new .2 gal/hr leak performed monthly which re- 120GRS. We have considered all the points
<br /> detector functions when installed is to intro- places the.1 gal/hr leak performed annually. herein stated and more and we meet the per-
<br /> duce a leak and see if it alarms. Now that you This option is EPA approved! But if it takes forrnances required. By those and other con-
<br /> have got past that hurdle,how often should amonth tofind a.2gal/hrleak,alotoffuel can sideration,all at a relatively low cost both to
<br /> you retest to verify that your line leak detector still be undetected.Therefore we atCAMPO/ procure and install.
<br /> continues to function? We at CAMPO/ MILLER have designed our line leak detec- Give us a try. C/M
<br /> MILLER feel so strongly about installation for to perform the.2 gal/hr leak test EVERY by Ernest A Flippi
<br /> and periodic testing of line leak detector,we DAY. CAMPO/MILLER
<br /> made it a part of our Third Party Test proce- Here's another fact that will be helpful to PO Box 1809,Porterville,CA 93258
<br /> dure. In real world situation for periodic you to know. Temperature differences (209)781-6862 Fax(209)781-7304
<br /> Electronic Line Leak Detectors Series LS300 Third Party Tested
<br /> LS300-120 PLUS-NEW. ANSI/UL 913 Tested
<br /> i
<br /> Performs 3 gal/hr Test&Precision Test
<br /> Self-Test and Signals.
<br /> LS300-120
<br /> Performs 3 gaVhr Test
<br /> Self-Test and Signals
<br /> LS300-120 XLC -NEW-
<br /> Performs 3 gal/hr Test ' The LS300 Series installs
<br /> Self-Test _ without piping modification,
<br /> LS300-120 GRS -:VEW- performance is tailored to the operating
<br /> Test Lube Lines&Satellite Lines ! conditions of the piping system.Installs in one hour.Signals leak
<br /> Performs 3 gal/hr Test - with visual,audible alarm,remote signaling and also turns off submersible pump,ifdesired.
<br /> Self-Test CAMPO/HOLLER PO Box 1809 Porterville,CA 93258 (209)781-6862 Fax(209)781-6862