Laserfiche WebLink
OIL EQUIPMENT SERVICE STATE 1.1c SE No. 323417 <br /> Division of Keith A. Tallia, Inc. CLASSIFICATION:A. C61. D40 <br /> Telephone: (209)754-1808 <br /> Post Pffice Box 950 <br /> 750 Industrial Way <br /> SAN ANDREAS, CALIFORNIA 95249 <br /> March 21 , 1988 <br /> San Joaquin Local Health District <br /> Environmental Health Division <br /> 1601 E . Hazelton Ave <br /> PO Box 2009 <br /> Stockton , CA 95201 <br /> Subject : EMERGENCY PLAN AND OVERFILL PROTECTION PLAN <br /> Site: Bob Cat Central <br /> 1113 Shaw Road <br /> Stockton , CA 95205 <br /> Facilities : 1 - 2,000 gallon double wall steel STIP-3 <br /> gasoline storage tank <br /> 1 - 2 , 000 gallon double wall steel STIP-3 <br /> diesel storage tank <br /> Type System: Pressure <br /> Product Piping: Double Wall <br /> Overfill Protection: Perkins welding 5 gallon containment <br /> containers around each fill pipe . <br /> Annular Monitoring: Visual via sticking each week day . <br /> Piping Monitoring: Visual each week day by observing <br /> contents of containment tub around <br /> submerged pump riser. Double wall <br /> piping is graded to drain back to <br /> this tub . <br /> The following functions are performed each work day by the <br /> shop foreman : <br /> 1 . The liquid level in each tank is measured and <br /> recorded. <br /> 2. The annular space on each tank is visually checked via a <br /> sticking for the presence of liquid and Jogged . I <br /> liquid is present it is checked to determine if it is <br /> water or product. This is also so noted on the log . <br /> 3. A visual check of the containment tubs around the 5ub- <br /> merged pump risers is made and logged . <br /> _ 1 - <br />