Laserfiche WebLink
OIL EQUIPMENT SERVICE STATE LICENSE No.323417 <br /> CLASSIFICATION: A-HA I.,C61 D40 <br /> Division of Keith A. Ta Ilia, Inc. STATE ENVIRONMENTAL ASSESSO No.01781 <br /> Telephone: (2 0)754-1600 <br /> Fax: (2(9)754-5726 <br /> LEAK DETECTOR TEST RECORD Post Of lice Box 950 <br /> 750 In dustrial Way <br /> SAN ANDREAS,CALIFORNIA 95249 <br /> Customer <br /> jDat <br /> Bob Cat Central /01 _. <br /> Location <br /> 1113 Shaw rd. , Stockton, CA 95205 <br /> Technician Product <br /> James P Hesketh Gasoline_ _ __ _ . <br /> Submersible Pump Identification <br /> Manufacturer Model No. Serial Number <br /> Tokheim 3/4hp Can not read <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Dete tar <br /> Campo Miller Diaphragm-type— Electronic <br /> Piston-type LS 300 Plus <br /> Tamper-proof seal installed? Yes No X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure-2 5 psi (para. 15) <br /> 2. Gallons per hour rate 3 (para.22) <br /> 3. Line pressure with pump shut off 22 psi (para.23) <br /> 4. Bleedback Test with pump off N/A ml (para. 26) <br /> 5. Step-through time to full flow N/A seconds(para. 30) <br /> 6. Leak detector stays in leak search position. (para. 42) Yes N/A <br /> No=N A <br /> LEAK DETECTOR TEST *Complete thermal expansion test <br /> Note: Noss=Leak detector fits test protocol before failing leak detector. <br /> Fail=Leak detector fails test protocol <br /> Pass–X_ Turbine Shut Down <br /> Fail__ <br /> 4/9/01 _ <br /> T n1ci in Date <br /> J es P. Hesketh <br />