Laserfiche WebLink
23417 <br /> OIL EQUIPMENT SERVICE STATE LICENSE No. <br /> CLASSIFICATION: A-IIA2.,C61D40 040 <br /> Division of Keith A. Tallia, Inc STATE ENVIRONMENTAL ASSESS01 t No.01781 <br /> Telephone: (21)9)754-1808 <br /> Fax: (2 9)754-5726 <br /> LEAK DETECTOR TEST RECORD Post O lice Box 950 <br /> 750Industrial Way <br /> SAN ANDREAS,CALIFORNIA 95249 <br /> Customer Date <br /> Bob Cat Central 4/9/01 <br /> Location <br /> 1113 Shaw Rd. , Stockton, CA 95205 <br /> Technician Product <br /> James P. Hesketh Diesel <br /> Submersible Pump Identification <br /> Manufacturet Model No. Serial Number <br /> Tokheim 3/4hp. Can not read----- <br /> Leak <br /> ead_ —Leak Detector Identification <br /> Manufacturer Description Other Style Leak Dett clor <br /> Campo Miller Diaphragm-type— Electronic <br /> Piston-type <br /> LS 300 Plus <br /> Tamper-proof seal installed? Yes No X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> I. Operating Pump Pressure 2 B psi (para. 15) <br /> 2. Gallons per hour rate 3 (para.22) <br /> 3. Line pressure with pump shut off 2 3 psi (para.23) <br /> 4. Bleedback Test with pump off N/A ml (para.26) <br /> 5. Step-through time to full flow N/A seconds(para. 30) <br /> 6. Leak detector stays in leak search position. (para. 42) yesA <br /> No <br /> LEAK DETECTOR TEST *Complete thermal expansion test <br /> Note: Pam=teakdetector fits test proiocol before failing leak detector <br /> Fail=teak detector fails test protocol <br /> pass_ <br /> Fail_K_ Does not go into alarm. <br /> 7 <br /> 4/9/01 <br /> I'e nician - -- Dat <br /> J es P. Hesketh <br />