Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Phillips Facility <br /> Tank #: 1 Test Date: 6/ 6/02 <br /> Product: Unleaded Regular Work#: 12901008 <br /> 9 - <br /> Test Method: Test Method: R.J. FTA <br /> Capacity: 9816 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 01071422 <br /> Liquid Volume(Gals): Line Drain Back(ml): 58 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 26 <br /> Coef. of Expansion: Metering Pressure(psi): 21 <br /> Water On Tank(in): L/D Test Rate(gph): 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? Yes <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 10:30:00 AM <br /> Test Method: ULLAGE Line End Time: 10:45:00 AM <br /> 7U11ageVolume(gals.): Line Start Level: 260 <br /> Ullage Test Time: Line End Level: 260 <br /> Ullage Vacuum(psi): Line Test Rate(gph): dWoo- <br /> Ullage Result: N/A Line Test Result: PASS <br /> old LD PLD failed <br /> 4 <br />